background image

7

Lowering a Fan (Applicable to Downflow Units) 

3.5

1. Remove the six screws 

and then the beam. 

2. Rotate the fan upward by 30 degrees, and 

pull the rotating shaft of the fan to the 
outermost side. 

4. After the fan rotates to the position shown in the 

figure, push the fan back to the horizontal position. 

5. Tighten the six screws on the beam and fan 

support, and connect the fan cables using the 
interconnection  terminal reserved in the cabinet.

3. Slowly rotate the fan by 90 degrees and ensure 

that the rotating shaft of the fan is on the 
outermost side. Exercise caution when handling 
the fan to avoid body injury. 

4

Installing the Outdoor Unit

Before installing the outdoor unit, keep the protective paperboard for the fins at the bottom 
to protect people from injuries during the installation. Remove it after installation.

The installation methods and distance requirements  for installing NetCol500-A060, 
NetCol500-A080,  and NetCol500-A120  outdoor units are the same. This section describes 
how to install a NetCol500-A060.  The NetCol500-A110  outdoor unit does not support vertical 
installation.

If the space does not meet the requirements  of the recommended  layout, you can use any of 
the layouts (applicable only to NetCol500-A060)  in the user manual. 

Summary of Contents for 52273539

Page 1: ...HUAWEI TECHNOLOGIES CO LTD NetCol8000 A 045 055 060 090 120 In room Air Cooled Smart Cooling Product Quick Guide Issue 05 Part Number 31500BLY Date 2021 10 20 ...

Page 2: ...ferential pressure sensor water sensor temperature and humidity T H sensor NetCol8000 A045U 2000 x 900 x 900 NetCol8000 A055D 2000 x 900 x 1000 NetCol8000 A060D 2000 x 1100 x 1000 NetCol8000 A060U 2000 x 1100 x 1000 NetCol8000 A090D 2000 x 1800 x 1000 NetCol8000 A120D 2000 x 2200 x 1000 Outdoor unit NetCol500 A060 52273539 1107 677 x 1094 x 1356 1219 Low temperature component NetCol500 A060 522735...

Page 3: ... list Auxiliary material Customers can purchase this type of materials from the supplier or other vendors Refrigerant refrigerant oil pipe component power cable and communications cable Optional material Customers can purchase this type of materials from the supplier based on application scenarios T H sensor micro differential pressure sensor water sensor and smoke sensor Engineering procurement m...

Page 4: ... a temperature control intelligent monitoring board that is the air cooled outdoor unit and water cooled module 52273539 52273541 Equipotential ground cable 16 mm Optional T H sensor cable teamwork control and monitoring communications cables shielded network cable of Cat 5e or higher specifications Optional Humidifier water inlet pipe Rigid pipe connection G 3 4 inch rigid pipe connector with int...

Page 5: ...e the internal pressure Find the saturation pressure corresponding to the measured outer surface temperature from the following table If the deviation between the saturation pressure and the measured internal pressure is greater than 0 2 MPa the refrigerant does not meet the requirements and needs to be replaced Mapping Between Saturation Temperatures and Pressures of R410A Saturation Temperature ...

Page 6: ...to use tools that are fully insulated when installing devices 4 Only engineers from the manufacturer or engineers certified by the agent are allowed to install commission and maintain the smart cooling product Otherwise personal injuries and device damage may be caused which is beyond the warranty range NetCol8000 A045 Upflow NetCol8000 A045 A055 090 Downflow Liquid pipe needle valve Exhaust pipe ...

Page 7: ...flow Liquid pipe needle valve Exhaust pipe needle valve Low pressure needle valve Liquid pipe needle valve Exhaust pipe needle valve Low pressure needle valve Securing to the Floor or Base 3 4 Removing Compressor Fasteners 3 3 Removing the Pallet 3 2 ...

Page 8: ...an is on the outermost side Exercise caution when handling the fan to avoid body injury 4 Installing the Outdoor Unit Before installing the outdoor unit keep the protective paperboard for the fins at the bottom to protect people from injuries during the installation Remove it after installation The installation methods and distance requirements for installing NetCol500 A060 NetCol500 A080 and NetC...

Page 9: ...llation Compact Installation Unit mm NetCol500 A060 NetCol500 A110 Make sure that no blockage is above the outdoor unit When installing an outdoor unit vertically do not place a low temperature component at the air exhaust vent Keep the low temperature component 600 2000 mm away from the outdoor unit NetCol500 A80 ...

Page 10: ...ed at the Needle Valves of the Outdoor Unit 4 2 b Install the four legs a Remove the corner fittings NetCol500 A060 A080 A120 Horizontal Installation Choose Either Horizontal or Vertical Installation 4 3 The strength level of the concrete platforms must be equal to or greater than C20 ...

Page 11: ...nce D2 NetCol500 A060 W1 250 D1 250 150 250 944 1064 NetCol500 A080 W1 250 D1 250 150 250 944 1894 NetCol500 A120 W1 250 D1 250 150 250 2038 1064 Concrete platform dimensions unit mm NetCol500 A110 Unit mm The strength level of the concrete platform must be equal to or greater than C20 Securing the legs to the concrete platforms ...

Page 12: ...lation 4 4 Model Block Width W1 Block Depth D Block Height H Center Distance W2 E NetCol500 A060 52273539 52273539 005 W1 300 D 500 150 250 1150 1037 NetCol500 A060 52273539 006 W1 300 D 500 150 250 1120 978 NetCol500 A080 W1 300 D 500 150 250 1920 1742 NetCol500 A120 W1 300 D 500 150 250 2120 1217 Concrete platform dimensions unit mm NetCol500 A060 A080 A120 The strength level of the concrete pla...

Page 13: ...500 A060 52273539 52273539 005 1287 1257 387 478 1037 1126 NetCol500 A060 52273539 006 1290 1260 447 538 978 1066 NetCol500 A080 2117 2087 387 478 1742 1830 NetCol500 A120 2259 2229 387 478 1217 2100 Interface dimensions unit mm ...

Page 14: ...controlled within the ranges of 4 C to 45 C and 5 RH to 90 RH respectively If the indoor installation position is ventilated it should be more than 5 km away from the sea or pollution sources such as salt lakes chemical plants mineral plants thermal power plants and coal mines Horizontal Installation on Concrete Bases Stacking Scenario A maximum of four layers of water cooled modules can be stacke...

Page 15: ...recommended to weld the pipes between the indoor and outdoor units then connect the two ends of the pipe to the indoor unit and outdoor unit Use a rubber hose to connect the nitrogen cylinder which connecting the reducing valve and the end of the copper pipe then fill nitrogen at 0 03 0 05 MPa into the copper pipe to avoid internal oxidation After the pipe in the middle is welded charge nitrogen i...

Page 16: ...d liquid pipe NetCol500 A110 1 Inverted U shaped trap 2 Oil traps 3 Tilted gas pipe 4 Tilted liquid pipe Side pipe routing Bottom pipe routing If the outdoor unit is higher than the indoor unit add a reverse U shaped trap at the liquid pipe The inverted U shaped trap must be at least 1 m higher than the bottom of the outdoor unit ...

Page 17: ... 3 1 Connect one end of the rubber hose to the nitrogen cylinder with a reducing valve and connect the other end to the refrigerant copper pipe in a higher position 2 Adjust the nitrogen reducing valve to set the nitrogen pressure to 10 bar and increase the pressure of the copper pipe 3 After drainage disconnect the rubber hose from the copper pipe and seal the two ends of the pipe using tape to p...

Page 18: ... A045 A055 A090 Downflow Bottom Piping Welding the Indoor Unit Ports 6 5 NetCol8000 A045 Upflow Bottom Piping NetCol8000 A060 A120 Downflow Bottom Piping NetCol8000 A060 Upflow Bottom Piping 1 Gas pipe 2 Liquid pipe ...

Page 19: ...18 NetCol8000 A060 Upflow Side Piping NetCol8000 A060 A120 Downflow Side Piping NetCol8000 A045 Upflow Side Piping NetCol8000 A045 A055 A090 Downflow Side Piping 1 Gas pipe 2 Liquid pipe ...

Page 20: ...ove the needle valve plugs in case of loss or damage Water Cooled Module NetCol500 A060 A080 A120 NetCol500 A110 Thermal insulation foam 5 8 inch liquid pipe 7 8 inch gas pipe 5 8 inch liquid pipe Thermal insulation foam 7 8 inch gas pipe Welding the Outdoor Unit Ports 6 7 ...

Page 21: ...pper pipe to a 5 8 inch connector Welding a Water Cooled Module 6 9 5 8 inch liquid pipe 7 8 inch gas pipe 7 Connecting Water Pipes Connecting a Humidifier Water Inlet Pipe 7 1 G 3 4 inch reserved connector with external screw threads G 3 4 inch adapter with internal screw threads Matched with the adapter 0 7 MPa pressure resistance Note 1 When plastic materials such as PA66 are used the recommend...

Page 22: ... Adapter 5 Hose clamp 3 Rigid pipe 6 Hose The drainpipe from the unit to the condensate branch pipe must have gradients 1 100 Significant upward trend and stagnant water is not allowed along the pipe NetCol8000 A045 Upflow NetCol8000 A045 A055 A090 Downflow NetCol8000 A060 Upflow NetCol8000 A060 A120 Downflow ...

Page 23: ...mpliance with the cable routing plan 2 The shielding layer of signal cables must be grounded 3 The outer insulation sheath should be retained when you route a cable through the waterproof connector 4 Power cables for the indoor and outdoor units should be bound using cable clips near the ports of the power module 5 Shielded cables cannot be used as power cables for outdoor units 6 The following fi...

Page 24: ...23 NetCol8000 A045 Upflow Connecting the Indoor Unit Power Cable 8 2 NetCol8000 A045 A055 A090 Downflow QFI QF2 QFI QF2 ...

Page 25: ...24 NetCol8000 A060 Upflow NetCol8000 A060 A120 Downflow QFI QF2 QFI QF2 ...

Page 26: ...o another outdoor unit if NetCol8000 A090 or NetCol8000 A120 is configured 3 The outdoor cables are sun and water proofed It is recommended that tubes be used for protection 4 If the outdoor unit is NetCo500 A120 connect the outdoor unit power cables to the QF1 and QF3 of the outdoor unit respectively 5 The outdoor unit must be powered by the indoor unit Connecting the Outdoor Unit Power Cable 8 3...

Page 27: ... an example If the indoor unit is NetCol8000 A090 or NetCol8000 A120 connect the outdoor unit signal cable to X503 terminals 1 2 and 3 or 5 6 and 7 of the indoor unit Air cooled outdoor unit The shield layer must be routed through the buckle and crimped properly Water cooled module and indoor unit The shield layer must be reliably connected to the nearby PE point Connecting the Signal Cable to an ...

Page 28: ...al pressure sensor and route the hose through the top of the cabinet to the supply air pipe plenum chamber There should be two binding points adjacent to the pressure inlet The distance between the binding point closer to the pressure inlet and the pressure inlet should not exceed 25 mm and the distance between two binding points is within 20 30 mm 3 Connect cables to the differential pressure sen...

Page 29: ...28 NetCol8000 A045 Upflow NetCol8000 A045 A055 A090 Downflow NetCol8000 A060 Upflow NetCol8000 A060 A120 Downflow ...

Page 30: ... outdoor unit Low temperature component power cable from the outdoor unit to the indoor unit Optional Connecting the Water Sensor 8 7 Water sensor cable Optional Connecting the T H Sensors Outside Cabinets 8 8 1 Connect the T H sensor cables The T H sensors in the aisles should be installed on the door frames of server cabinets and 1 5 m 33 U away from the ground After the sensors are secured set ...

Page 31: ... OFF ON ON OFF Hot aisle 5 temp humid 25 ON OFF OFF ON ON OFF 2 Set the DIP switches on the T H sensors Optional Connecting Teamwork and Monitoring Network Cables 8 9 No Name Description 1 Running indicator 2 Alarm indicator 3 FE_1 port FE teamwork control 4 CAN_IN port CAN teamwork and RS485 monitoring cascading 5 RS485 12V port Connecting to T H sensors 6 USB port Connecting to a WiFi module or ...

Page 32: ... HT RS485 5 White and blue RS485 R RS485 HT RS485 6 Green FE RX FE RX 7 White and brown CANH 8 Brown CANL GND Pin Color COM FE Port RS485 Monitoring 4 Blue RS485 5 White and blue RS485 Connect the COM FE port on the main control module of the last smart cooling product in each group to the RS485 port on the host CAN Teamwork RS485 Monitoring 2 Connect teamwork and monitoring communications cables ...

Page 33: ...tocol CAN Modbus TCP SNMP Customers can purchase Huawei s switch and NetEco as the monitoring system FE Teamwork FE Monitoring Networking Teamwork Monitoring Protocol MAC_CAN Modbus TCP SNMP Customers can purchase Huawei s switch and NetEco as the monitoring system ...

Page 34: ...is greater than or equal to 100 m use the group based ring networking mode 1 Connecting units with odd numbers Connect the FE_1 port of the unit with an odd number to the FE_2 port of the unit with the next odd number 2 Connecting units with even numbers Connect the FE_2 port of the unit with an even number to the FE_1 port of the next unit with an even number 3 Connect FE_2 of No 1 unit and FE_1 ...

Page 35: ...door unit The height of the reserved space must be greater than that of the cap 1 Remove the cap front panel using a Phillips screwdriver Place the cap on the top of the cabinet 2 Secure the cap using M5 tapping screws 3 Secure the cap front panel to the frame and adjust the angle of the front panel blade 900 mm wide indoor unit 2 PCS respectively on the front and the rear and 3 PCS respectively o...

Page 36: ... valve and rubber tube nut Tighten the nut when you feel cold air coming out from the nut 3 Put the refrigerant steel vessel upside down on an electric balance Clear the reading on the balance 4 Open pressure gauge valves and the refrigerant steel vessel valve to charge refrigerant 5 The amount of refrigerant charged must be more than half of the total charge amount calculated and less than the to...

Page 37: ...ol8000 A045U including a low temperature component NetCol500 A060 NetCol500 A12 system 1 NetCol500 A120 system 2 32 3 32 3 L 10 x 0 21 32 3 L 10 x 0 28 NetCol8000 A090D system 1 NetCol500 A060 NetCol500 A120 system 1 9 4 9 4 L 10 x 0 21 9 4 L 10 x 0 28 NetCol500 A080 13 4 13 4 L 10 x 0 21 13 4 L 10 x 0 28 NetCol8000 A090D system 2 NetCol500 A060 NetCol500 A120 system 2 9 4 9 4 L 10 x 0 21 9 4 L 10...

Page 38: ...00 A080 15 5 15 5 L 10 x 0 23 15 5 L 10 x 0 31 NetCol500 A110 22 22 L 10 x 0 23 22 L 10 x 0 31 NetCol8000 A060U including a low temperature component NetCol500 A080 42 42 L 10 x 0 23 42 L 10 x 0 31 NetCol8000 A120D system 1 NetCol500 A080 15 5 15 5 L 10 x 0 23 15 5 L 10 x 0 31 NetCol500 A110 22 22 L 10 x 0 23 22 L 10 x 0 31 NetCol8000 A120D system 2 NetCol500 A080 15 5 15 5 L 10 x 0 23 15 5 L 10 x...

Page 39: ...se a single system unit as an example You need to perform leak checking vacuuming and precharging refrigerant on both systems of a dual system unit Nut Reducing valve Vacuum pump Exhaust pipe needle valve Scenario Without a Low Temperature Component NetCol8000 A060 A120 Downflow Nut Reducing valve Vacuum pump Low pressure needle valve 1 Leak checking 2 Vacuuming 3 Precharging refrigerant Exhaust p...

Page 40: ...g 3 Precharging refrigerant Scenario with a Low Temperature Component NetCol8000 A045 A055 A090 Downflow Scenario with a Low Temperature Component NetCol8000 A060 A120 Downflow Nut Reducing valve Nitrogen cylinder Electronic scale Refrigerant cylinder Vacuum pump Low pressure needle valve 1 Leak checking 2 Vacuuming 3 Precharging refrigerant Exhaust pipe needle valve Liquid pipe needle valve ...

Page 41: ... pressure needle valve Exhaust pipe needle valve 1 Leak checking 2 Vacuuming 3 Precharging refrigerant Scenario Without a Low Temperature Component NetCol8000 A060 Upflow 1 Leak checking 2 Vacuuming 3 Precharging refrigerant Low pressure needle valve Exhaust pipe needle valve Nut Reducing valve Nitrogen cylinder Electronic scale Refrigerant cylinder Vacuum pump ...

Page 42: ...ant cylinder Vacuum pump Low pressure needle valve Exhaust pipe needle valve Liquid pipe needle valve Low pressure needle valve Exhaust pipe needle valve Nut Nitrogen cylinder Electronic scale Refrigerant cylinder Vacuum pump Low pressure needle valve Reducing valve Scenario with a Low Temperature Component NetCol8000 A060 Upflow 1 Leak checking 2 Vacuuming 3 Precharging refrigerant ...

Page 43: ...he smart cooling product is in shutdown mode After powering on the compressor starts preheating and the system generates an alarm indicating that the compressor is preheating for 12 hours Do not start the smart cooling product before the preheating ends Choose Running Device Details Compressor to query the remaining preheating time 1 Turn on the smart cooling product switch in the upstream power d...

Page 44: ...Diagnostic Mode Enter Set the compressor speed to 3000 rpm Choose Maint Diagnostic Mode Exit and tap Shutdown on the home screen If there is no water supply clear the humidifier commissioning item After wizard startup lift the low liquid level detector After at least 5 seconds choose Running Device Details Humidifier to check that Low liquid level states is Triggered Choose Running Device Details ...

Page 45: ...st be unique and the unit with the smallest address is the master unit 3 Networking mode The networking mode set on the screen must be consistent with the actual networking mode 4 Enable teamwork CAN resistor Set the parameter if CAN teamwork is used Set the parameter to ON for the first and last units 5 Number of systems in this group Specifies the number of units in a group The value is an integ...

Page 46: ...tdown 2 Turn off the main switches of the indoor unit and outdoor unit 3 Optional If the smart cooling product needs to be powered off for maintenance or for a long time switch off its circuit breaker on the PDF 11 Optional Power Off ...

Page 47: ...Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...

Reviews: