UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
157
Figure 5-11
Login
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
e.
On the homepage, choose
Monitoring
>
Control
, and click
Inverter On
. In the
displayed dialog box, click
OK
to start the inverter, as shown in
Figure 5-12
Starting the inverter
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
Step 7
Ensure that the UPS transfers to normal mode. View the system running diagram to check that
the
Bypass mode
alarm disappears on the LCD. Check the UPS three-phase output voltage
and frequency by viewing the AC Output data on the LCD, as shown in
. Use a multimeter to measure the three-phase output voltage and frequency.