Technical specifications
:
Temperature
Humidity
Measuring
range
0℃~50℃(internal)
-30℃~70℃(external)
0%RH~100%RH
temperature
accuracy
±0.5℃
≤±3%RH(25℃,20-90%RH)
Working
range
-10℃~60℃
0%RH~100%RH(non-condensing)
Power
supply
DC16~30V (suggest 24V)
Output
Voltage 0~5V / 0-10V
Current
4-20mA
Canning
material
ABS Engineering Plastics
Wire mode Voltage 4 lead terminals
Current
3 lead terminals
Look-up table for analog output:
0-5V
0-10V
4~20mA
Humidity
0%RH
0
0
4mA
100%RH
5v
10v
20mA
Temperature
0℃ (-30)
0
0
4mA
50℃ (70)
5v
10v
20mA
Order of connection for voltage
:
1 2 3
4
5
6
T_out
RH_out
Gnd
VCC
Temperature output Humidity output Negative wire Positive wire
Order of connection for current
:
1 2 3 4
5
6
T_out
RH_out
VCC
Temperature output Humidity output Positive wire
Installation instructions
:
Fist fix the drain pan onto the right installation position
,
then buckle the watch case upon the installed
drain pain.