HTW HTWMO2041M01R32 Owners And Installation Manual Download Page 19

It can only be repaired by the method suggested by the equipment’s manufacturer.

Qualification requirement for installation and maintenance man

Installation notes

The air conditioner is not allowed to use in a room that has running fire (such as fire source, working coal gas ware, 
operating heater).

Maintenance notes

Welding

Check whether the maintenance area or the room area meet the requirement of the nameplate.

- It’s only allowed to be operated in the rooms that meet the requirement of the nameplate.

Check whether the maintenance area is well-ventilated.

- The continuous ventilation status should be kept during the operation process.

Check whether there is fire source or potential fire source in the maintenance area.

- The naked flame is prohibited in the maintenance area; and the “no smoking” warning board should be hanged.

Check whether the appliance mark is in good condition.

- Replace the vague or damaged warning mark.

If you should cut or weld the refrigerant system pipes in the process of maintaining, please follow the steps as below: 

It is not allowed to drill hole or burn the connection pipe.
The air conditioner must be installed in a room that is larger than the minimum room area. The minimum room area is 
shown on the nameplate or following table a.
Leak test is a must after installation.

table a- Minimum room area ( m  )

2

Charge amount (kg)

≤1.

2

1.

3

1.

4

1.

5

1.

6

1.

7

1.

8

1.

9

2

2.

1

2.2

2.3 2.4

2.5

/

/

/

/

14.

5

16.

8

19.

3 22 24.8 27.8 3

1

34.3 37.8

41.

5 45.4 49.4 53.6

5.2 6.

1

7

7.9 8.9

1

0

11.

2

12.

4

13.

6

1

5

16.

3

17.

8

19.3

1.

6

1.

9

2.

1

2.4 2.8 3.

1

3.4 3.8

4.2

4.6

5

5.5

6

1.1 1.

3

1.

4

1.

6

1.

8 2.

1

2.3 2.6 2.8

3.

1

3.4 3.7

4

floor location

wall mounted

window mounted

ceiling mounted

Minimum

room

2

area( m  )

INSTALLER

SAFETY OPERATION OF FLAMMABLE REFRIGERANT

All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the 
authoritative organization and the qualification for dealing with the refrigeration system recognized by this industry. 
If it needs other technician to maintain and repair the appliance, they should be supervised by the person who 
bears the qualification for using the flammable refrigerant.

Filling the refrigerant

Safety instructions for transportation and storage

a. Shut down the unit and cut power supply
b. Eliminate the refrigerant
c. Vacuuming
d. Clean it with N2 gas
e. Cutting or welding
f. Carry back to the service spot for welding

The refrigerant should be recycled into the specialized storage tank.

Make sure that there isn’t any naked flame near the outlet of the vacuum pump and it’s well-ventilated.

Use the refrigerant filling appliances specialized for R32. Make sure that different kinds of refrigerant won’t 
contaminate with each other.

After filling is finished, please do the leakage detection before test running; another time of leak detection should be 
done when it’s removed.

Please use the flammable gas detector to check before unload and open the container.

No fire source and smoking.

According to the local rules and laws.

The refrigerant tank should be kept upright at the time of filling refrigerant.

Stick the label on the system after filling is finished (or haven’t finished).

Don’t overfilling.

19

Summary of Contents for HTWMO2041M01R32

Page 1: ...OWNER S AND INSTALLATION MANUAL OUTDOOR UNIT MULTISPLIT Thanks for choossing our product Please read carefully this manual before using the product ENGLISH M01 R32 ...

Page 2: ...l characteristics technical data and accessories of this appliance may be changed without notice This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should b...

Page 3: ... to indicate risk of property damage Indicates a hazard that would be assigned a signal word WARNING or CAUTION WARNING CAUTION DANGER NOTICE CONFORMITY AND RANGE GENERAL INFORMATION Please read this owner s manual carefully before operating the unit and keep it carefully for consultation Only use the air conditioner as instructed in this booklet These instructions are not intended to cover every ...

Page 4: ...d repair be necessary contact your nearest authorized Service Centre The appliance shall be stored in a room without continuously operating ignition electric heater Do not pierce or burn s instructions only Be aware that refrigrants not contain odour Read specialist s manual Please read this operating manual carefully before operating the unit to the material objects for reference THE REFRIGERANT ...

Page 5: ...ctric shock Donot spray wateronindoorunit It may cause electric shock ormalfunction After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoid deformation or fire hazard Maintenance must be performed by qualified professionals Otherwise it may cause personal injury or damage Do not repair air conditioner by yourself It may cause electric sh...

Page 6: ...ir switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner should be properly grounded Incorrect grounding may cause electric shock Don t use unqualified power cord Properly connect the live wire neutral wire and grounding wire of power socket Do not put through the power before finishing installation If the supply cord is d...

Page 7: ...and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please contact the supplier for a new one Avoid extending the wire by yourself For the air conditioner with plug the plug should be reachable after finishing installation For the air conditioner without plug an circuit break must be installed in the line If you need to relocate the air con...

Page 8: ... turned on or off according to your requir ement automatically please do not turn on or turn off the unit freque ntly otherwise disadvantage effect may be caused to the unit Rated voltage of this air conditi oner 220 240V 50Hz The com pressor will vibrate sharply if the voltage is too low resappointed amage to refrigerating system Electrical component are easy to damage if the voltage is too high ...

Page 9: ...32 HTWMO3061M01R32 Warning Be sure to cut off the power supply before cleaning the air conditioner otherwise electric shock might happen Wetting of air conditioner may cause the risk of electric shock Make sure not to wash your air conditioner in any case This product must not be disposed together with the domestic waste This product has to be disposed at an authorized place for recycling of elect...

Page 10: ...oduct has to be disposed at an authorized place for recycling of electrical and electronic appliances Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner Only use soft dry cloth moist cloth clean the air conditioner cabinet The temperature of refrigerant circuit will be high please keep the interconnection cable away from the copper tube Note The abo...

Page 11: ...Indoor side DB WB Outdoor side DB WB Maximum cooling 32 23 43 26 Maximum heating 27 24 18 The operating temperature range outdoor temperature for cooling only unit is 15 43 for heat pump unit is 15 43 Indoor side DB WB Outdoor side DB WB Maximum cooling 32 23 43 26 Maximum heating 27 24 18 The operating temperature range outdoor temperature for cooling only unit is 15 43 for heat pump unit is 20 4...

Page 12: ...ings ofthe unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wiring regulations HTWMO2041M01R32 1 Remove the handle at the right side plate of the HANDLING After having removed the packaging check that the contents are intact and complete The outdoor unit must always be kept upright Handling must be done by s...

Page 13: ...tioner connecting cable connecting cable To the power supply B brown black HTWMO3071M01R32 An all pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring Wrong wire connection may cause malfunction of some electric components After fixing cable ensure that leads between connection to fixed point have some space The connection pipes and ...

Page 14: ...ing cable ensure that leads between connection to fixed point have some space An all pole disconnection switch having a contact separation of at least 3mm in all pole should be connected in fixed wiring The connection pipes and the connectiong wirings ofthe unit A unit B unit C and unit D must be corresponding to each other respective The appliance shall be installed in accordance with national wi...

Page 15: ...ndle 1 Remove the handle at the right side plate of the outdoor unit one screw Note The above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased Wrong wire connection may cause malfunction of some electric components After fixing cable ensure that leads between connection to fixed point have some space An...

Page 16: ...5 50 70 75 Φ12 Φ19 Diameter mm Φ9 52 Φ16 15 20 Φ6 18K unit need to be installed the indoor unit Caution Installation Must be Performed in Accordance with the NEC CEC by Authorized Personnel Only conversion joint 18K MODE INDOOR UNIT Connect to the indoor unit Refrigerant fluid direction of fiow 3 way valve 2 way valve inlet 2 Turn 8 Secure 7 Turn to open fully 2 Turn 8 Secure 6 Openby 1 4 turn 7 T...

Page 17: ...other refrigerant than R32 MAINTENANCE INSTALLER INSTALLATION DIMENSION DIAGRAM INSTALLER 30cm Space to the cover or above 30cm 50cm Air inlet side or above or above Space to the wall 30cm Space to the cover or above 30cm 50cm Air inlet side or above or above Space to the wall 30cm Space to the cover or above 30cm 50cm 200cm Air inlet side or above or above Space to the wall Air outlet side or abo...

Page 18: ...s Have the length of refrigerating pipe and refrigerant charge amount been recorded Has the unit been safely grounded Problems Owing to Improper Installation The unit may drop vibrate or make noises May cause unsatisfactory cooling heating effect May cause condensation and water dropping May cause condensation and water dropping The unit may bread down or the components may be burned out The unit ...

Page 19: ...2 4 13 6 15 16 3 17 8 19 3 1 6 1 9 2 1 2 4 2 8 3 1 3 4 3 8 4 2 4 6 5 5 5 6 1 1 1 3 1 4 1 6 1 8 2 1 2 3 2 6 2 8 3 1 3 4 3 7 4 floor location wall mounted window mounted ceiling mounted Minimum room 2 area m INSTALLER SAFETY OPERATION OF FLAMMABLE REFRIGERANT All the work men who are engaging in the refrigeration system should bear the valid certification awarded by the authoritative organization an...

Page 20: ...C Industria 13 l Polígono Industrial El Pedregar 08160 Montmeló Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info htwspain com www htwspain com ...

Reviews: