INSTALLATION AND MAINTENANCE MANUAL FOR 

VITRIFIED TANKS AND INTERACUMULATORS

1.- 

Generalities

 

This document is intended for the installer and the end 

user. Therefore, after commissioning of the installation, it 

is necessary to ensure that this manual is delivered to the 

end user or the person responsible for managing the 

installation.

The products that are the object of this document have 

been manufactured according to the 2014/68 / CE 

directive relative to the pressure devices in accordance 

with the fluid contained in them and the conditions of use 

contemplated for their use.

2.- 

Instalation and maintenance

The tanâ must alïays be sheltered from atmospheric 

agents, on a solid base, verifying before installation that 

there is sufficient space for the extraction of anodes, 

resistances, instrumentation and to facilitate the opening 

of the manhole.

It must be ensured that the room intended to contain the 

tank is provided with an access to the exterior with the 

appropriate dimensions to facilitate the passage of the 

apparatus without the need to carry out any demolition 

work. The guarantee does not cover the occasional costs 

derived from the breach of this point.

It must also be ensured that the local referral is equipped 

with a drainage system appropriate to the volume of the 

accumulator and other possible devices. The guarantee 

does not cover the occasional costs derived from the 

breach of this point.

The inlet connection of the domestic cold water to the 

domestic water network must be made by means of a 

hydraulic safety group that includes at least a shut-off 

tap, a check valve, a check valve control device, a 

control device hydraulic load interruption, all accessories 

necessary to use the accumulator efficiently and safely.

If the pressure of the domestic water supply system 

could exceed the design pressure value of the tank, a 

pressure reducing valve should be installed as far as 

possible from the same tank. In order to prevent 

pressure shocks that damage the tank, it is always 

necessary to install an expansion vessel.

For tanks with water

-fed primary at a temperature of less 

than 100 ºC, the expansion system must consist of an 

exhaust valve, of counterïeight or spring type, ïith an 

outlet diameter (mm) not less than (V / 5) 1 / 2, ïhere V is 

the volume (lts) of the tanâ, ïith a minimum of 15 mm. The 

valve must be set at a pressure not higher than the 

design pressure. In addition to the exhaust valve, it is 

advisable, to avoid continuous openings, to install an 

expansion vessel of the closed membrane type.

In order for the product to have effective protection 

against electrochemical corrosion and to fulfill the 

guarantee, it is necessary to always provide cathodic 

protection for each material. HTW provides as standard in 

its internally vitrified tanks magnesium anodes that must 

be replaced periodically. The correct installation of the 

tanks (according to the instructions provided with the 

material), as well as proper maintenance, is essential to 

guarantee the useful life of the tank. To avoid eventual 

galvanic wandering currents, it is essential to connect the 

tank to an earth connection. Failure to comply with these 

rules invalidates the guarantee offered by HTW.

The progressive consumption of the magnesium anode 

can vary depending on the nature of the water and the 

conditions of use. It is necessary to program the periodic 

replacement of the magnesium anode, with a maximum 

periodicity of 18 months.

The minimum periodicity for cleaning the accumulator is 

one year, according to RD 865/2003 for the prevention 

and control of legionellosis. Cleaning and maintenance is 

essential to guarantee the life of the accumulator.

Maintenance and cleaning tasks must be recorded in the 

maintenance log, in accordance with article 8 of RD 

865/2003. If disinfection is necessary, it may be done by 

thermal or chemical means, complying with Annex 3 of 

the aforementioned Royal Decree.

Summary of Contents for ASF HTW-IVSF-150ASF

Page 1: ...VSF 500ASF ES EN MANUAL DE INSTALACI N INSTALLATION MANUAL Por favor lea atentamente este manual antes de usar este producto Please read carefully this manual before using the product Gracias Thank yo...

Page 2: ...MANUAL DE INSTALACI N ESPA OL ASF INTERACUMULADOR VITRIFICADO HTW IVSF 150ASF HTW IVSF 200ASF HTW IVSF 300ASF l HTW IVSF 500ASF...

Page 3: ...valor de presi n de dise o del dep sito hay que instalar una v lvula reductora de presi n lo m s lejos posible del mismo dep sito Con el fin de prevenir los golpes de presi n que da an al dep sito sie...

Page 4: ...eracumulador A Entrada de agua de red B Puntos consumo agua sanitaria C Hacia instalaci n calefacci n D Recirculaci n E Desag e 1 Acumulador 2 Caldera Generador t rmico 3 Vaso de expansi n 4 Grupo de...

Page 5: ...ASF INSTALLATION MANUAL ENGLISH VITRIFIED INTERACCUMULATOR HTW IVSF 150ASF HTW IVSF 200ASF HTW IVSF 300ASF l HTW IVSF 500ASF...

Page 6: ...k a pressure reducing valve should be installed as far as possible from the same tank In order to prevent pressure shocks that damage the tank it is always necessary to install an expansion vessel For...

Page 7: ...accumulator assembly diagram A Mains water inlet B Points of sanitary water consumption C Towards heating installation D Recirculation E Drain 1 Accumulator 2 Boiler Thermal generator 3 Glass of expa...

Page 8: ...ura m vil listado IMPORTANT INFORMATION FOR CORRECT DISPOSAL OF THE PRODUCT IN ACCORDANCE WITH EC DIRECTIVE 2002 96 EC At the end of its working life the product must not be disposed of as urban waste...

Reviews: