All vent pipes must be glued, properly supported, and the exhaust
pitched a minimum of 1/4” per foot back to the heater to allow
drainage of condensate. When placing support brackets on vent
piping, the first bracket must be within 1 foot of the water heater
and the balance of 4 foot intervals on the vent pipe. Venting must be
readily accessible for visual inspection from the first three feet from
the heater.
NOTE:
These drawings are meant to demonstrate system venting only.
The installer is responsible for all equipment and detailing required by
local codes.
Figure 13 - Unbalanced Venting - Roof Exhaust and Sidewall Intake