background image

18 

 

I.CHARGING THE SYSTEM 

 

Closed Loop Glycol 

 

Solar Tank 

Fill the solar tank with water. Do this by opening the cold water isolation ball valve to the solar tank. 
Inspect all fittings for leaks. The solar collector loop should be pressure tested with air (25 lbs.) before you 
pressurize the solar collector loop with glycol. Mix the DowFrost propylene glycol and distilled water in 
accordance with the data sheet in the back of the manual. The charging process will require a low flow 
diaphragm pump to fill and pressurize the collector loop. 
 

Solar Collector 

Connect the discharge side of the pressure pump to the fill valve. Place the pump suction side hose in the 
glycol solution. Close the ball valve (#11). Connect a second hose to the drain valve (#10) and place the 
other end of the hose in the empty bucket. 
 

TOTAL COLLECTOR LOOP FLUID CAPACITY IN GALLONS* 

1. One Collector System 

3.5 gallons 

2. Two Collector System 

4.5 gallons 

 

*Assumes a total 100’ pipe run using ¾” Type M hard copper tubing. 

The solar heat exchanger has a 1.5 gallon fluid capacity. 

 

Open the upper fill valve (#18) and allow the pressure from the expansion tank to push the water in the 
glycol loop back to prime the pressure pump. When the hose in the bucket containing the glycol mixture 
stops bubbling, you may begin charging the collector loop with glycol. With both fill and drain valves open, 
run the low flow diaphragm pump until the glycol mixture begins flowing into the empty bucket. Quickly 
switch the hose from the empty/return bucket to the bucket containing the glycol mixture. Continue to 
circulate the fluid using the pressure pump until the bubbling has stopped and the air has been purged. 
 
After charging the collector loop, shut the lower drain valve (#10) and let the pressure pump drive up the 
loop pressure to the appropriate level (generally in the range of 25 psi). To more accurately calculate the 
proper pressure, measure the height of the solar collector above the tank and divide this number by 2.31, 
then add 20 psi to this number. 
 

 

The pressure in the glycol loop should not exceed 45 psi when the system is in operation on a sunny day. 
Contact your solar contractor if the collector loop exceeds the threshold. 
 
After pressurizing the solar system, run the circulator and allow the air to purge out of the vent. Once 
purged, monitor pressures and check for leaks before insulating pipes. Pressure should then be about 25 
psi. 
 
Above ground piping must be insulated with a wall thickness of at least ¾”. A 1” thickness is required in 
areas prone to hard freeze conditions. Above ground insulation must be protected from ultraviolet 
degradation. All piping must be supported at a maximum interval of 10’ and the piping supports must not 
crimp or compress the insulation. 

J. COMMISSIONING THE SYSTEM 

 

Closed Loop Glycol 

 
After the glycol loop has been charged and pressure is around 25 psi (check gauge on solar heat 
exchanger) set the solar control to the desired settings. Solar controls come with default settings that will 
work in most installations. If it is a cloudy day, you may have to activate the circulator pump. Once the 

Summary of Contents for PH130-119S

Page 1: ...m described in this manual when properly installed and maintained meets the minimum standards established by the SRCC This certification does not imply endorsement or warranty of this product by the S...

Page 2: ...t symbol indicates a potentially hazardous situation which if not avoided may result in property damage FOREWORD This manual is intended to be used in conjunction with other literature provided with t...

Page 3: ...CGA No B149 latest version from Canadian Gas Association Laboratories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 Also Canadian Electrical Code C 22 1 from Canadian Standards Association 5060...

Page 4: ...SOLAR PANEL INSTALLATION 8 J COLLECTOR LOOP PIPE INSULATION 9 K COLLECTOR PIPING 9 L COLLECTOR SENSOR PLACEMENT 10 PART 3 WATER HEATER INSTALLATION 10 A INSTALLATION CHECKLIST 10 B POTABLE WATER PIPIN...

Page 5: ...t be done by a licensed professional who is qualified and experienced in the installation service and maintenance of solar hot water systems B WATER TEMPERATURE ADJUSTMENT If the solar water heater is...

Page 6: ...ents in the Phoenix Solar Water Heating System include the solar collector s a Phoenix Solar Water Heater a circulator pump a differential solar control and an expansion tank Depending on the type of...

Page 7: ...arked for that purpose The system components should carry temperature and pressure ratings equivalent to the design of the solar collector To ensure system is appropriate for installation climate the...

Page 8: ...PANEL INSTALLATION The contractor shall obtain all required permits and approvals for installing the solar system The installation shall conform to all federal state and local regulations governing s...

Page 9: ...ype of material Any above ground exterior pipe insulation is subject to UV degradation and must be wrapped with foil tape or painted with two coats of high quality water based acrylic resin coating as...

Page 10: ...copper two conductor PVC insulated with a PVC UV rated gray jacket suitable for exterior use Use Eastman Wire Cable no 5704 Beldon Wire and Cable no 8461 or equal The sensor bundle must be placed unde...

Page 11: ...ate codes or warranty will be void It is also necessary to use both thread tape and pipe dope on all mechanical connections The potable water piping is located on the side of your solar water heater a...

Page 12: ...igure 5 Run type M or larger copper pipes or flex line sets to and from the collector following the direction of supports penetrations and other relative items Only copper cast iron or brass are to be...

Page 13: ...ta Sheet in the back of this manual The collector loop must be charged with a mixture of heat transfer fluid and distilled or deionized water The use of regular tap water as a mixing agent is prohibit...

Page 14: ...mperature differentials Solar Controller The solar controller turns on or off the circulator depending on heat gained from solar operation The controller also limits overheating in the solar water hea...

Page 15: ...r feed lines to control discharge to an acceptable and safe temperature This also increases the amount of hot water that is drawn from the solar water heater by not allowing the incoming water to full...

Page 16: ...16 F PHOENIX SOLAR PIPING WITH AIR HANDLER Figure 6 This drawing is meant to demonstrate system piping concept only...

Page 17: ...and upper and lower tank temperatures H CIRCULATOR SIZING The circulator pump must be sized for the related piping and pressure drop of the heat exchanger The graph in Figure 8 represents the pressure...

Page 18: ...et Quickly switch the hose from the empty return bucket to the bucket containing the glycol mixture Continue to circulate the fluid using the pressure pump until the bubbling has stopped and the air h...

Page 19: ...the water heater free of sediment 3 Clean and inspect the solar collector 1 Dirt or film which may have settled on the surface may affect performance Check collector supplier information for cleaning...

Page 20: ...PRECAUTIONS MUST BE TAKEN TO AVOID PERSONAL INJURY FROM CONTACT WITH HOT WATER AND TO AVOID PROPERTY DAMAGE BEFORE operating lever check to see that a discharge line is connected to the valve directi...

Page 21: ...21 Figure 9 LP 204 L...

Page 22: ...22 Figure 10...

Page 23: ...23 Figure 11...

Page 24: ...Solar system incorrectly installed Check installation 4 Leaking plumbing or open hot water faucet s Make sure all faucet s are closed and check water meter Not enough hot water 1 Heater undersized Re...

Page 25: ...25...

Page 26: ...26...

Page 27: ...ncentration of propylene glycol increases to greater than 80 percent INSPECTION AND TREATMENT OF HEAT TRANSFER FLUID You can quickly determine the condition of your fluid by examining its appearance a...

Page 28: ...PHYSICIAN IN RESPONSE TO THE REACTION OF THE PATIENT CONSULT DOW CHEMICAL 24 HOUR EMERGENCY 1 989 636 4400 SYSTEM MODELS SOLAR COLLECTOR COMPANY MODEL OF COLLECTORS PH 80 HTP HP 30 SC 1 AET AE32E 1 SU...

Page 29: ...29...

Page 30: ...30 MAINTENANCE NOTES...

Page 31: ...ate of Installation Installer s Code Name Product Serial Number s Comments Installer s Phone Number Signed by Installer Signed by Customer IMPORTANT NOTES Customer Please only sign after the installer...

Reviews: