HT7051 - HT7051N
EN - 12
5.2.1 Configuration of the test parameters for FIX mode
a. By cyclically pressing the
SET/DISPLAY MEM
key, it is possible to select the
following parameters:
Minimum value of the insulation (MIN) in a range between 0,01M
- MAX
Maximum value of the insulation (MAX) in a range between (MIN) - 10T
Test time value in a range between (00min:05sec) - (99min:59 sec)
b. Press the arrow keys to change the value of the parameters (a long pressing of the
keys allows a rapid change of the values)
c. Press the
MODE/CLEAR SMOOTH
key to remove the limit values set for the
parameters. The display shows the message "no" to indicate that there is no limit set.
d.
After setting, press the
SAVE
key to save the changes made or press the
ESC/RECALL MEM
key to exit without saving and return to the previous screen