HST HP101 User & Installation Manual Download Page 4

                                                                 

Notification Appliance Circuits(Sounder)

2 NACs, Special Application

Maximum NAC Current Rating 

1 Amp maximum per circuit

NAC End-of-line Resistor

10K ohms 1/2W  5%

FAULT Relay rating

2A & 30VAC, resistive

Alarm( Auxiliary ) Relay rating 

2A & 30VAC, resistive

1.3 Fire Alarm System Limitations

An automatic fire alarm system – in general is made up of smoke, heat & other
detectors, manual call points, audible warning devices, fire alarm control panels with
remote notification capability, which can supply early warning of a developing fire.
Such a system, on the other hand, is unable to assure protection against property
damage or loss of life resulting from a fire.

The manufacturer recommends that smoke and/or heat detectors must be positioned
throughout a protected premise following the recommendations of the current edition
of   the  EN  Standard,  manufacturer’s   recommendations  contained   in   the  Guide  for
proper Use of System Smoke Detectors, which is made available at no charge to all
installing dealers. A study by the Federal Emergency Management Agency (an agency
of the United Europe) indicated that smoke detectors may not go off in as many as
35% of all fires. A fire alarm system may not provide timely or sufficient notice, or
might not function, for a diversity of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as
in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second-
floor detector, for example, may not sense a first-floor or basement fire.

Particles or combustion or “smoke” from a developing fire may not reach the sensing
chambers of smoke detectors because:

Barriers such as closed or partially closed doors, walls, or chimneys may 
inhibit particle or smoke flow.

Smoke particles may become “cold,” stratify, and not reach the ceiling or 
upper walls where detectors are located.

Smoke particles may be blown away from detectors by air outlets.

Smoke particles may be drawn into air returns before reaching the detector.

The amount of “smoke” present may be insufficient to alarm the smoke detectors.
Smoke detectors are designed to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the location of detectors, the
detectors will not go into alarm. Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photo electronic sensing chambers tend to
detect  smoldering fires better than flaming fires, which have  little visible smoke.
Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires

- 4 -

Summary of Contents for HP101

Page 1: ... Fire Alarm Control Panel 4 16 Zones User Installation Manual IMPORTANT This manual should be left with the panel after installation We reserve the right to change product specifications without prior notice ...

Page 2: ...E 7 2 2 MOUNTING THE ENCLOSURE 8 2 3 AC POWER CONNECTION 9 2 4 BATTERY INSTALLATION 9 2 5 ZONE INSTALLATION 10 2 6 NAC SOUNDER OUTPUT CIRCUIT INSTALLATION 10 2 7 RELAY OUTPUTS 10 2 8 RINGING THE ALARMS REMOTELY 11 2 9 SIGNALING FIRE TO ANOTHER PANEL 11 2 10 CONNECT TO REPEATER 12 2 11 MAIN PCB BOARD 12 2 12 INNER DOOR LABEL WIRING DIAGRAM 13 3 CONTROL PANEL OPERATION 14 4 LED INDICATORS 15 5 FAULT...

Page 3: ...e following key features 4 8 or 16 conventional input zones 2 notification appliance circuits NAC Sounder with built in synchronization for ANSI 3 41and Gentex The panel comes with a 3 amp power supply Dedicated alarm and trouble relays 1 RS485 can be able to connect repeaters Housed in a 383mm W x 295mm H x 87mm D metal enclosure Enclosure supports two 12V 7Ah backup batteries 1 2 Electrical Spec...

Page 4: ... might not function for a diversity of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in or behind walls on roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level or floor of a building A second floor detector for example may not sense a first floor or basement fire Particles or combustion or smok...

Page 5: ...y to report a fire Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building Any warning device may fail to alert people with a disability or those who have recently consumed drugs alcohol or medication Please note that Strobes can under certain circumstances cause seizures ...

Page 6: ...ments To ensure proper system operation this product must be tested in accordance with NFPA 72 after any programming operation or change in site specific software Re acceptance testing is required after any change addition or deletion of system components or after any modification repair or adjustment to system hardware or wiring All components circuits system operations or software functions know...

Page 7: ...ndling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the installation operating and programming manuals These instructions must be followed to avoid damage to the control panel and associated equipment FACP operation and reliability depend upon proper installation by a...

Page 8: ...sonnel and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order 2 2 Mounting The Enclosure Install the enclosure as follows 1 Carefully unpack the system components and inspect for any damage due to shipping 2 Mount the enclosure in a clean dry vibration free area where extreme temperatures are not encountered The location s...

Page 9: ...binet via a knock out hole Attach the brown live wire from the source to the terminal labeled L terminal Attach the blue neutral wire from the source to the terminal labeled N terminal Attach the ground wire from the source to the terminal labeled E terminal Figure 2 2 AC power wiring connection 2 4 Battery Installation The batteries are placed at the bottom of the enclosure The panel is fully pro...

Page 10: ...it Installation The control panel has 2 built in output notification appliance circuits NAC Figure 2 5 shows output circuit 1 wired as a class B NAC output Observe the polarity of the wiring and the placement of the 10K end of line EOL resistor located at the very end of the class B wiring Figure 2 5 Sounder bell wiring connection 2 7 Relay Outputs Each panel has 2 forms C relays the relays are de...

Page 11: ...s shown below when panel B closes its auxiliary contacts panel A will go into fire If the zone on panel A is set to non latching it will automatically reset when panel B opens its auxiliary contacts If both panels need to signal fire to each other simply duplicate the circuit substituting panel A for panel B and vice versa 11 Sense Zone Sense Zone Panel A 510R Resistor 4K7 EOL AUXILIARY CONTACTS C...

Page 12: ...rm control panel can connect 64 repeaters in the same RS485 communication wires The default setting for RS485 JP1 jump is set to position 2 which EOF of RS485 is zero ohm For the end repeater of RS485 the jump JP1 should set to position 1 which the EOF of RS485 is 120 ohm 2 11 Main PCB Board 12 ...

Page 13: ... e P e r m 2 8 V t e r m i n a l t h e a l a r m s d e v i c e s o n t h e N A C w i l l s o u n d B a t t e r y S i z e 2 x 1 2 V R e q u i r e d Z o n e 1 1 6 c i r c u i t s M a x i m u m N u m b e r o f D e t e c t o r s p e r Z o n e i s 3 0 s m o k e d e t e c t o r m a n u l c a l l p o i n t h e a t d e t e c t o r s m o k e d e t e c t o r E O L R e s is t o r 4 7 K m a x 3 0 d e v i c e ...

Page 14: ... button Silencing the fault alarm and sounder If a fire or fault is detected the panel will automatically activate the alarm circuits To silence the alarms press the Silence button once In the alarm silenced condition press the Silence button once the sounder will be reset Using the disable function The panel allows the user to selectively disable the sense zones and the alarm zones To enter disab...

Page 15: ...ry power condition is low or completely gone the Fault indicator comes on and the Battery LED become yellow Alarm Red LED This Indicator is lit when an alarm condition exists in the system initiated by smoke detectors heat detectors sprinkler flow switches manual pull stations manual call points or other initiating devices Along with the indicator on the panel notification appliances such as horns...

Page 16: ...one wiring Short circuit on the sense zone wiring Detector head removal Check all detectors and call points on the sense zone indicated Check wiring is as in example diagrams and ensure the end of line monitor is a 4K7 resistor or an active end of line device Fault LED and Sounder NAC zone fault LED flashing buzzer sounding Faults monitored are Open circuit on the Sounder NAC zone wiring Short cir...

Page 17: ...Ensure batteries are connected correctly and battery leads are secure Note Date Time Zone Event Action Required Date Completed Initials 17 ...

Reviews: