HLogic Security Technology Co., Ltd
www. hstfire .com
Document Ref: M2215-04
Issue: 5.5
01/2017
Note:
Maximum wiring resistance is 50 ohms.
Note
: During the installation, Make the rib of the detector align with the rib on the base until it drops into place.
(see figure 3)
Note
: Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may
not completely prevent airborne dust particles from entering the detector. Therefore, We recommends the removal of
detectors before beginning construction or other dust producing activity.
Be sure to remove the dust covers from any sensors that were left in place during construction as part of returning the system
to service.
Remote LED
The remote indicator is connected between terminals 1 and 4 as showing Figure 2. The remote indicator must be current
limited to 20mA @24V. Maximum. Not limiting current could result in damage to the detector or cause a no alarm condition.
Tamper-Resistance
The detector include a tamper-resistant capability that prevents their removal from the bracket without the use of a tool.
Testing
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service.
Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having
Jurisdiction (AHJ). Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
Direct Heat Method (Hair dryer of 1000 – 1500 watts)
1. From the side of the detector, direct the heat toward the sensor. Hold the heat source about 6 inches (15cm)
away to prevent damage to the cover during testing.
2. The LEDs on the detector should light when the temperature at the detector reaches the alarm set point. If the LEDs fail to
light, check the power to the detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested. If the detectors still fail
these tests they should be returned for repair.
Maintenance
Before removing the detector, notify the proper authorities that the smoke detector system is undergoing maintenance and
will be temporarily out of service.
1. Counterclockwise rotation detector, remove it from the mounting base is removed.
2. Remove the detector cover by pressing firmly on each of the four removal tabs that hold the cover in place.
3. Use a vacuum cleaner or compressed air to remove
dust and debris from the heat sensor.
4. Replace the cover using the LEDs to align the cover
and then gently pushing it until it locks into place.
5. Reinstall the detector.
6. Test the detector as described in TESTING.
7. Reconnect disabled circuits.
8. Notify the proper authorities that the system
is back on line.
60mm
Figure 3. Install the detector
Rib
Detector
Base
Installed
HLogic Security Technology Co.,Ltd,
B1-4F XinHaoSheng High Tech Park,YongHe Rd,Baoan,SZ,China
17
2115CPR2016-06-10
EN54-5
HD202B Addressable heat detector
Fire detection and fire alarm systems installed in and around buildings.
According to Construction Products Regulation EU N° 305/2011