Summary Screen Setting
Function
Line
Method
Result
Options /
Comments
Summary Display
Lines & dynamic point
setting
SL1…32
SL(x)x=abc…
Assign
Screen Line
text as information or in
relation to SP1…32
Alpha/numeric, 40
characters max.
SP1…32
SP(x)x=nnn
Assign
Screen Point
dynamic point value
Point #
SLL1…32
SLL(x)x=nnn
Assign
Screen Line Logic
point who’s value
>0 will cause the related screen line to appear
at the top of the display (alarm state for
instance)
Point #
Manual Override / Release
Values that have been manually set will be indicted in HyperTerminal by an
M
tag next to the displayed
value.
Manualled physical inputs (points 1…8 & 17…24) will revert to ‘Auto’ after being Released or after a
power reset. Physical outputs will retain the Manual setting after a power reset if the Manual state is
Written (
W
) before being released, thereby making the Manual state the power-up default state. If the
‘Remember’ function is enabled for an output the last commanded state is valid after a power reset.
Function
Enter
Result
Options /
Comments
Manual a
Digital
Point #=1, 0
Digital on or off
1=On
0=Off
Example: 37=1
Manual an
Analogue
Point #=0…
n
0…100% block output
Block range 0….max
Example: 25=50 (AO1 50% output
/ 5Vdc output)
Release
Manual
overrides back
to ‘Auto’
*
R
R=1…92
Inputs will return to auto state/value.
Other points will remain at manualled
state/value until power reset or
commanded
Example 1: R
All overrides are cleared
Example 2: R=9
DO1 (point 9) only return to Auto
Reset pulse
accumulator
100…800=6
1700…2400=6
DI or UI with pulse accumulator
config. (UI or DI setting 6) is reset to
zero
Example: 800=6