background image

Please read carefully

Read through these instructions completely before commencing installation. Retain for future use.
1. This product shall be installed in accordance to AS/NZS 3000 Wiring Rules.
2. Regulations concerning the discharge of air must be fulfilled. Local building codes may require venting to the outside.
3. This product must be installed at least 2.2m above floor level. 
4. Do not install within 120cm of a stove or inside a shower recess.
5. Cross Ventilation:

Ventilation products must have an adequate source of external air to ensure rated performance.
Steam and air will only be exhausted through the fan if there is sufficient flow of air through the room. Ensure adequate inlets exist through windows, 
vents or under the door. Airflow path from the inlet to the fan should ideally pass over the source of steam or air to be removed from the room.
Restrictions on replacement air entering the room to be ventilated, or pressure-differentials between the room and outside air will significantly reduce 
the exhaust fan’s performance.

6. Compliance with Section 6 Damp Situation of AS/NZS 3000 Wiring Rules:

No part of the unit may be located directly above any part of the bath or shower recess or enclosure.
The unit must be installed within zones 2 and 3 only. For further information, refer to AS/NZS 3000.

7. Unit Orientation:

The unit must be installed to ensure the housing outlet and ducting is oriented in parallel to any roofing structures or supports. Refer to image below 
for correct installation orientation. Orientation which forces the unit to be ducted into a 90° bend immediately after the fan outlet will cause a significant 
performance reduction.

8. Duct Size and Length:

The unit must be installed with Ø150mm duct using the adaptor supplied to ensure optimum extraction and performance. The maximum recommended 
duct length is 3m. The graph below shows the unit’s performance with 3m of duct. Longer ducts will reduce the unit’s performance. 

9. Duct Routing:

As the back pressure increases the unit’s performance is reduced. Airflow will be reduced with bends in duct or squashing of duct. Every 90° bend/
elbow results in approx 20% reduction in the unit’s performance. 
Please refer to the graph below, an almost linear relationship between back pressure and fan performance proves just how critical correct installation 
of the exhaust fan is in relation to performance.  

-20

0

20

40

60

80

100

120

0

50

100

150

200

250

300

Back Pressure (PA)

Air Flow (m

3

/H)

EFD01 series

(Ducted- Ø150mm x3m)

Summary of Contents for EFD01RDWE

Page 1: ... White Supply Voltage 230 240V a c 50Hz Power Rating 40W max Max Airflow Rate Non ducted 330m3 hr Max Airflow Rate Ducted Ø150mm x 3m 250m3 hr Protection Class Class II Duct Requirement Ø150mm Ceiling Cut out Size Ø298mm Projection into Ceiling 190mm Protrusion from Ceiling 26mm Grille Size Ø372mm 350 x 350 mm EFD01RDWE EFD01SQWE EFD01RDWE EFD01RDMS EFD01SQWE ...

Page 2: ...ted directly above any part of the bath or shower recess or enclosure The unit must be installed within zones 2 and 3 only For further information refer to AS NZS 3000 7 Unit Orientation The unit must be installed to ensure the housing outlet and ducting is oriented in parallel to any roofing structures or supports Refer to image below for correct installation orientation Orientation which forces ...

Page 3: ...at one end and insert a pencil at the other end and scribe a circle figure 2 3 Cut out around this line figure 3 4 Remove grille from the exhaust fan 5 Attach duct adaptor to duct with duct tape figure 4 6 Ensure that a power outlet is installed in the ceiling near the intended position of the exhaust fan Ensure that power to the outlet is off Plug the exhaust fan into this outlet figure 5 7 Attac...

Page 4: ...the duct will not run back into the fan housing 11 Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances 12 This product has been designed for domestic or similar uses and is not suitable for a commercial installation 13 This product is not suitable for installation in hazardous and or corrosive areas 14 The material in t...

Reviews: