Installation
25
User Manual
Before mounting the system to the rack, select the way you wish to place the system. Pay atten-
tion to the airflow within the rack cooling, connector and cabling options.
While planning how to place the system, review the following points:
• Make sure the system air flow is compatible with your installation selection. It is import-
ant to keep the airflow within the rack in the same direction.
• In case there are cables that cannot bend within the rack, or in case more space is needed
for cable bending radius, it is possible to recess the connector side or the FRU side by 3”
or 4” (7.62 or 10.16cm) by optional placement of the system’s rails.
• The FRU side is extractable. Mounting the sliding rail inverted to the system will allow
you to slide the FRU side of the system, in and out.
Step 1.
Install 10 cage nuts into the desired 1U slots of the rack: 4 cage nuts in the non-extractable
side and 6 cage nuts in the extractable side.
Figure 18: Installing the Cage Nuts
Step 2.
Mount both of the outer rails (C+D) into the rack (as illustrated in
), and use 8
standard pan-head screws (E) to fix them to the rack. Do not tighten the screws yet.
Figure 19: Mounting the Outer Rails into the Rack
Step 3.
If cable accommodation is required, route the power cable and/or Eth cable through either
of the outer rails.
Step 4.
Attach the switch to the left and right inner rails (A+B), by gently pushing the switch chas-
sis’ pins through the slider key holes, until locking occurs.