06/20/2017                                                        700-FPA 

Figure 1 

4.

 

Construction of the Remote LP Tank System Enclosure  

 
IMPORTANT: 

Only select models of Push Button / Match Lit (FPPK and MLFPK) fire pits are permissible for small 

tank use- please see HPC Product catalog, visit www.hpcfire.com or contact your HPC Dealer for details. 

IMPORTANT: 

Locate the hose out of pathways where people may trip over it or in areas where the hose may be 

subject to accidental damage.  

For an enclosure using an LP tank system, follow these recommended specifications: 

 

You must follow local codes. 

 

IMPORTANT:

 The remote LP Tank / Enclosure should be a minimum of 36” from the fire pit. 

 

One side of the enclosure shall be completely open; OR 

 

For an enclosure having four sides, a top, and a bottom: 

o

 

At least two ventilation openings shall be provided in the side walls of the enclosure, located within 5 in 
(127mm) of the top of the enclosure, equally sized, spaced at a minimum of 180 degrees, and 
unobstructed. The opening(s) shall have a total free area of not less than 1in

2

lb (14.2 cm

2

kg).  

See Figure 1. 

o

 

Ventilation opening(s) shall be provided at floor level of the enclosure and shall have a total free area of 
not less than ½ in

2

/lb (7.1cm

2

/kg) of stored fuel capacity. If ventilation openings at floor level are in a 

side wall, there shall be at least two openings. The bottom of the openings shall be 1 in (25.4mm) or less 
from the floor level and the upper edge no more than 5 in (127mm) above the floor level. The openings 
shall be equally sized, spaced at a minimum of 180 degrees and unobstructed.  See Figure 1. 

 

Every opening shall have minimum dimensions so as to permit the entrance of a 1/8 in (3.2mm) diameter rod. 

 

Ventilation openings in sidewalls shall not communicate directly with other enclosures of the appliance. 

 

 
   
 
  

 
 
 
 
 
 
 

 

The cylinder valve shall be readily accessible for hand operation. A door on the enclosure to gain access to the 
cylinder valves is acceptable, provided it is non-locking and can be opened without the use of tools. Designs using 
a cover to gain access to the cylinder and cylinder valve shall be provided with handles or equivalent at a 
minimum of 180 degrees apart to facilitate lifting of the cover. 

 

The enclosure for the LP-gas cylinder shall isolate the cylinder from the burner compartment to provide: 

o

 

Shielding from radiation; 

o

 

A flame barrier; and 

o

 

Protection from foreign material. 

 

There shall be a minimum clearance of 2 in (50.8mm) between the floor of the non-disposable LP-gas cylinder 
enclosure and the ground. 

 

The design of the enclosure shall be such that: 

o

 

A non-disposable LP-gas cylinder can be connected, disconnected, and the connections inspected and 
tested outside the cylinder enclosure; and 

o

 

Those connections which could be disturbed when installing the cylinder in the enclosure can be leak 
tested inside the enclosure.  

 

LP Tank Size 

Top Opening 

Bottom Opening 

20 LB (9.1 KG) 

20 in

2

 (130 cm

2

10 in

2

 (65 cm

2

30 LB (13.6 KG) 

30 in

2

 (195 cm

2

15 in

2

 (100 cm

2

 

 

 

LP Tank Enclosure Specifications 

2 Openings for each top and bottom - 180

o

 apart 

From LP tank base to bottom of opening - Max. 1" (25.4mm) 
From floor to base of LP tank - Min. 2" (50.8mm) 