3.

 

Press the Standby button to select the nominal voltage 
configuration. The LED associated with the old input 
voltage parameter turns off, and the LED associated with 
the new input voltage parameter illuminates solid green. 

  

NOTE:

  Only one nominal utility voltage can be 

configured. When setting voltage configuration 
parameters, selecting an On value for any one 
parameter automatically sets the other possibilities  
to Off. 

4.

 

To enable the Wiring Fault parameter, press the On 
button to advance the cursor to the Utility LED, then press 
the Standby button. The LED illuminates solid green.  
This parameter is disabled by default, and should only 
be enabled for line-to-neutral connections. Enabling this 
feature for line-to-line power sources causes a  
false alarm. 

5.

 

To configure the UPS for the number of connected ERMs, 
press the On button to advance the cursor to the load 
LED associated with the number of ERMs attached to  
the UPS. 

6.

 

Press the Standby button to select the appropriate ERM 
configuration. The associated LED illuminates  
solid green. 

7.

 

To save the configuration settings and exit Configure 
mode, press the Test/Alarm Reset button. 

  

NOTE:

  Configure mode times out after 2 minutes. If 

the Test/Alarm Reset button has not been pressed, any 
new selections are not saved. 

 

UPS front panel controls 

 

The front panel is shown with the bezel removed. 

       

Item Description 

Function 

On button 

Powers up the UPS 

Standby button 

Places the UPS in Standby mode 

Test/Alarm Reset 
button 

 

Silences UPS alarms 

 

Tests the LEDs 

Configure button 

Places the UPS in Configure mode 

 

 

UPS front panel LED indicators 

 

The front panel is shown with the bezel removed. 

        

Item LED 

description 

1 Overload 

76% to 100% load 

51% to 75% load (2 ERMs) 

26% to 50% load (1 ERM) 

0% to 25% load (0 ERMs) 

6 General 

Alarm 

7 On 

Battery 

8 Battery 

Fault 

Site Wiring Fault 

10 Utility 

11 

Configure Mode On 

 

For more information, see "LED and audible alarm 
troubleshooting" in the user guide. 

Legal notice 

© Copyright 2003, 2006 Hewlett-Packard Development Company, L.P. 

The information contained herein is subject to change without notice. The only 
warranties for HP products and services are set forth in the express warranty 
statements accompanying such products and services. Nothing herein should 
be construed as constituting an additional warranty. HP shall not be liable for 
technical or editorial errors or omissions contained herein. 

 

Summary of Contents for UPS R5500 ERM

Page 1: ...nance and service of this product must be performed by individuals who are knowledgeable about the procedures precautions and hazards associated with AC power products 75 kg 167 lb This symbol indicates that the ERM exceeds the recommended weight for one individual to handle safely WARNING To reduce the risk of personal injury or damage to the equipment observe local occupational health and safety...

Page 2: ...ections to the branch circuit such as the use of power strips Electrical requirements All models require a dedicated unshared branch circuit suitably rated for the specific UPS as stated in Input specifications in the user guide Readying the equipment 1 Check the battery recharge date specified on the label that is affixed to the shipping carton IMPORTANT Do not use the battery if the recharge dat...

Page 3: ... rails for integrated shipping If the unit is to be shipped in an HP 9000 or 10000 series rack 1 Remove the hex nuts flat washers and lock washers from the mounting rail 2 Install the rail reinforcement plates and tighten using the hex nuts with captive washers included in the kit instead of the nuts included with the rail 3 Install the rear mounting brackets using hex nuts Wait until the unit is ...

Page 4: ... a hazardous condition CAUTION Always plan the rack installation so that the heaviest item is on the bottom of the rack Install the heaviest item first and continue to populate the rack from the bottom to the top 1 Install the mounting rails Installing the mounting rails on page 2 2 With one person on each side of the carton lift the chassis and lower it to the floor in front of the rack 3 Install...

Page 5: ...t parameter Available settings Parameter Associated LED Explanation when LED is illuminated Nominal Voltage Setting 200 208 Nom General Alarm red Nominal utility voltage level is set to 200 208 VAC factory default for 326529 D71 220 Nom On Battery red Nominal utility voltage level is set to 220 VAC 230 Nom Battery Fault red Nominal utility voltage level is set to 230 VAC factory default for 326529...

Page 6: ...onfigure mode press the Test Alarm Reset button NOTE Configure mode times out after 2 minutes If the Test Alarm Reset button has not been pressed any new selections are not saved UPS front panel controls The front panel is shown with the bezel removed Item Description Function 1 On button Powers up the UPS 2 Standby button Places the UPS in Standby mode 3 Test Alarm Reset button Silences UPS alarm...

Reviews: