Battery Maintenance
4-2
HP Uninterruptible Power System T2200 XR Models User Guide
Determining When to Replace Batteries
When the Bad Battery/Low Battery LED (1) illuminates red, batteries may need to be
replaced within 30 to 60 days.
1
Figure 4-1: Bad Battery/Low Battery LED
To check a battery alarm, initiate a UPS battery self-test to verify that battery replacement is
required. If the Bad Battery/Low Battery LED (1) remains red, replace the batteries as soon
as possible.
NOTE:
Depending on usage and environmental conditions, the batteries should last three to six years.
For more information on initiating a self-test, refer to the section, “Initiating a Self-Test,” in
Chapter 2.
Obtaining New Batteries
New batteries may be required within 30 to 60 days when the Bad Battery/Low Battery LED
illuminates red. Obtain spare batteries for the UPS when this occurs.
HP supplies spare battery packs for this UPS. The UPS spare battery kit part number is
240796-001
.
CAUTION:
Because of the short shelf life of the battery, avoid storing a battery spare as a
backup. Do not maintain an onsite inventory of spare batteries unless a procedure to keep the
stored batteries charged is implemented.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com