Page 10
792519-001 Edition 1
ENGLISH
2.3 Display functions
Press the
button to activate the menu options. Use the and buttons to scroll through the menu structure. Press
the
button to select an option. Press the
button to cancel or return to the previous menu.
Menu map for Display Functions.
Main menu
Submenu
Display information or Menu function
Measurements
—
Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Control
Load Segments
Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active fault (UPS restart required)
Restore factory settings
Returns all settings to original values
Reset power usage
Clears power usage measurements
Settings
Local settings
Sets general parameters
Input / output settings
Sets Input and output parameters
ON / OFF settings
Sets on and off conditions
Battery settings
Sets battery configuration
Fault log
—
Displays event log or alarms
Identification
—
UPS Type/Part Number/Serial Number/Firmware release/Com card
address
2.4 User settings
The following table displays the options that can be changed by the user.
Description
Available settings
Default settings
Local settings
Language
[English] [French] [German] [Spanish]
[Italian] [Portuguese] [Russian]
Menus, status, notices and alarms, UPS
fault, event log data and settings are in all
supported languages.
English
User selectable when the UPS
is powered the first time.
LCD settings
Allows LCD screen brightness and contrast
to be adapted to room light conditions.
—
Audible alarm
[Enabled] [Disabled on battery] [Always
disabled]
Allows you to enable or disable the audio
alarm if an alarm occurs.
Yes
In/Out settings
Output voltage
Low voltage: [100V] [120V] [125V]
High voltage: [200V] [208V] [220V]
[230V] [240V]
User selectable when UPS is
powered for the first time.
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower input volt-
age to 70V before UPS transfers to battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity
[High] [Low]
High: For sensitive equipment, the
UPS will easily transfer to battery when
utility conditions deteriorate.
Low: For less sensitive equipment, the UPS
will not transfer to battery when utility
conditions deteriorate.
High
Load segments - Auto
start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected equipment is powered
after the specified delay.
Group 1: 3 s
Group 2: 6 s
Continued
2. User Interface