Removal and replacement procedures 66
o
For rack models, extend the server from the rack (on page
6.
Remove the access panel.
7.
Remove the air baffle (on page
8.
Remove the fan cage (on page
9.
Remove all hot-plug SAS or SATA drives connected to the failed backplane ("
10.
Disconnect all cables from the drive backplane.
11.
Loosen the thumbscrews and remove the drive backplane.
To replace the component, reverse the removal procedure.
8-SFF drive cage and backplane
To remove the component:
1.
Do one of the following:
o
For tower models, open and remove the tower bezel ("
o
For rack models, if installed, remove the security bezel ("
Remove the security bezel (optional)
on page
2.
Power down the server (on page
3.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
4.
Do one of the following:
o
For tower models, place the server on a flat, level surface with the access panel facing up.
o
For rack models, extend the server from the rack (on page
5.
Remove the air baffle (on page
6.
Remove the fan cage (on page
7.
Disconnect all the cables from the drive backplane.
Summary of Contents for ProLiant ML350 Gen9
Page 5: ...Contents 5 Index 123 ...
Page 13: ...Customer self repair 13 ...
Page 14: ...Customer self repair 14 ...
Page 15: ...Customer self repair 15 ...
Page 18: ...Illustrated parts catalog 18 ...
Page 64: ...Removal and replacement procedures 64 LFF configuration SFF configuration ...
Page 91: ...Component identification 91 o Rack orientation 24 LFF drives o Tower orientation ...
Page 109: ...Cabling 109 Embedded SATA cabling LFF configuration SFF configuration ...
Page 112: ...Cabling 112 o SFF configuration o LFF configuration SAS Expander cabling One SAS Expander ...
Page 113: ...Cabling 113 o LFF configuration o SFF configuration ...