System Unit
System Unit
System Unit
System Unit
Dimensions
Dimensions
Dimensions
Dimensions (H x W x D)
(with bezel)
12.04 x 17.32 x 27.4 in (30.58 x 44 x 69.6cm)
Weight
Weight
Weight
Weight
(approximate)
Maximum
(all hard drives, power
supplies, and processors
installed)
160lb (72 kg)
Minimum
(one hard drive, 2 power
supply, and 4 processor
modules installed)
147 lb (67 kg)
Input Requirements
Input Requirements
Input Requirements
Input Requirements
(per 3 power supplies non
redundant)
Rated Line Voltage
90 - 132 VAC
180 - 264 VAC
Rated Input Current
24A @ 100 VAC
14A @ 200 VAC
Rated Input Frequency
47 to 63 Hz
Rated Input Power
2400W @ 100-120 VAC
2800W @ 200-240 VAC
BTU Rating
BTU Rating
BTU Rating
BTU Rating
Maximum
8189 BTU/hr @ 100-120 VAC
9554 BTU/hr @ 200-240 VAC
Power Specifications
Power Specifications
Power Specifications
Power Specifications
NOTE:
NOTE:
NOTE:
NOTE: To review typical system power ratings use the HP Power Advisor
which is available online located at url:
www.hp.com/go/proliant-energy-
efficient
or
www.hp.com/go/hppoweradvisor
Click on the system of interest. Example: DL785 G6
Follow the instructions of the next screens
Power Supply Output
Power Supply Output
Power Supply Output
Power Supply Output (per
power supply)
Rated Steady-State Power 800 W (at 100 VAC),
1200 W (at 200 VAC)
Maximum Peak Power
800 W (at 100 VAC),
1200 W (at 200 VAC)
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature
System Inlet Temperature Operating
10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change is
10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed. System performance may be reduced if
operating with a fan fault or above 30°C (86°F).
Non-operating
-30° to 60° (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).
Relative Humidity
Relative Humidity
Relative Humidity
Relative Humidity
(non-condensing)
Operating
10% to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature, non-
condensing.
Non-operating
5% to 95% relative humidity (Rh), 38.7°C
(101.7°F) maximum wet bulb temperature, non
condensing.
Altitude
Altitude
Altitude
Altitude
Operating
3050 m (10,000 ft). This value may be limited by
QuickSpecs
HP ProLiant DL785 Generation 6 (G6)
HP ProLiant DL785 Generation 6 (G6)
HP ProLiant DL785 Generation 6 (G6)
HP ProLiant DL785 Generation 6 (G6)
Technical Specifications
DA - 13432 Worldwide — Version 14 — April 14, 2011
Page 41