Removal and replacement procedures 48
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Disconnect all peripheral cables and power cords from the rear panel.
4.
Do one of the following:
o
Extend the server from the rack (on page
o
Remove the server from the rack (on page
5.
Remove the access panel ("
6.
Remove the air baffle (on page
7.
Remove the fan blank.
CAUTION:
To prevent improper cooling and thermal damage, do not operate the server
unless all bays are populated with either a component or a blank.
To replace the component, reverse the removal procedure.
Hot-swap fan
WARNING:
To reduce the risk of personal injury from hot surfaces, allow the drives and the
internal system components to cool before touching them.
CAUTION:
To prevent damage to electrical components, properly ground the server before
beginning any installation procedure. Improper grounding can cause ESD.
To remove the component:
1.
Power down the server (on page
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Do one of the following:
o
Extend the server from the rack (on page
o
Remove the server from the rack (on page
Summary of Contents for ProLiant DL60 Gen9
Page 5: ...Contents 5 Documentation feedback 111 Index 112 ...
Page 13: ...Customer self repair 13 ...
Page 14: ...Customer self repair 14 ...
Page 15: ...Customer self repair 15 ...
Page 23: ...Illustrated parts catalog 23 ...
Page 33: ...Removal and replacement procedures 33 o Secondary PCI riser cage o PCI blank ...
Page 95: ...Component identification 95 Fan locations ...
Page 110: ...Acronyms and abbreviations 110 UID unit identification USB universal serial bus ...