System Fans
Standard
6 Hot plug, redundant fans (individually removable)
Maximum
6 Hot plug, redundant fans (individually removable)
Required Cabling
For required cabling information, refer to the HP Web site at
http://h18000.www1.hp.com/products/servers/proliantDL585/
OS Support
Windows Server 2003
Red Hat Enterprise Linux
SUSE Linux Enterprise Server
Sun Solaris
VMware Virtualization Software
NOTE:
For a more complete and up-to-date listing of supported OSs and versions, please visit our
OS Support Matrix at:
http://www.hp.com/go/supportos
.
NOTE:
For an up-to-date listing of the latest drivers available for the HP ProLiant DL585 G2,
please see:
http://www.hp.com/support
.
NOTE:
For more Linux OS support & certification information, please visit our the ProLiant &
BladeSystem Server Linux matrix at:
http://h18004.www1.hp.com/products/servers/linux/hpLinuxcert.html
NOTE:
For more information on HP's Certified and Supported ProLiant Servers, please visit the
VMware Server Support Matrix at:
http://h18004.www1.hp.com/products/servers/software/vmware/hpvmwarecert.html
NOTE:
For more complete and up-to-date information on how to buy server operating systems
from HP please visit the OS product site at:
http://h18004.www1.hp.com/products/servers/software/OEM.html
Rack Airflow
Requirements
Rack 10000 series Cabinets
The increasing power of new high-performance processor technology requires increased cooling
efficiency for rack-mounted servers. The 10000 Series Racks provide enhanced airflow for
maximum cooling, allowing these racks to be fully loaded with servers using the latest processors.
CAUTION:
If a third-party rack is used, observe the following additional requirements to ensure
adequate airflow and to prevent damage to the equipment:
Front and rear doors: If your 42U server rack includes closing front and rear doors,
you must allow 5,350 sq cm (830 square inches) of hole evenly distributed from top to
bottom to permit adequate airflow (equivalent to the required 64 percent open area for
ventilation).
Side: The clearance between the installed rack component and the side panels of the
rack must be a minimum of 7 cm (2.75 inches).
CAUTION:
Always use blanking panels to fill all remaining empty front panel U-spaces in the rack.
This arrangement ensures proper airflow. Using a rack without blanking panels results in improper
cooling that can lead to thermal damage.
NOTE:
For additional information, refer to the Setup and Installation Guide or the Documentation
CD provided with the server, or to the server documentation located in the Support section at the
following URL:
www.hp.com/servers/dl585
.