Removal and replacement procedures 15
Removal and replacement procedures
Safety considerations
The HP POD 40c NA is listed to the UL 69050 standard as an Information Technology Product and Classified
according to the NEC, NFPA-70, 2008.
The HP POD 40c NA is not suitable for long term personnel occupancy.
The safety information is specific to the people operating and maintaining the components of the HP POD
40c NA.
IMPORTANT:
All plumbing to and from the HP POD 40c NA must be completed by a licensed
plumber.
IMPORTANT:
All wiring in and around the HP POD 40c NA must be completed by a licensed
electrician.
Operator safety
The HP POD 40c NA is not habitable or suitable for human occupancy. The HP POD 40c NA is Listed as a
Product that provides service access areas for periodic maintenance and service. These areas must be
controlled and available for use only by owner-authorized personnel and qualified personnel who are
trained in the maintenance and service of the HP POD 40c NA components.
WARNING:
To avoid the risk of personal injury or loss of life, all personnel must comply with PPE
requirements when opening or working inside areas of the HP POD 40c NA that are marked as
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ).
WARNING:
To avoid the risk of personal injury, hearing protection must be worn at all times
when working inside the HP POD 40c NA.
WARNING:
To avoid the risk of personal injury or damage to the equipment, do not insert
anything inside the electrical busways, except for the approved HP busway drop boxes.
Before completing the installation of the HP POD 40c NA, the customer, or a designated agent, is
responsible for completing any Environmental Health and Safety evaluation of the HP POD 40c NA or any
attached structural component purchased through HP. The customer, or their designated agent, must also
complete an arc flash assessment and breaker coordination study of the HP POD 40c NA and the associated
electrical supply system for operation and maintenance. The individual or organization that completes the
arc flash assessment must also create and provide all required labeling for all electrical panels on the HP
POD 40c NA.