6. Technical Specifications
6.2 HP T750 G4 INTL UPS, HP T1000 G4 INTL UPS, and HP T1500 G4 INTL UPS
HP T750 G4 INTL UPS
HP T1000 G4 INTL UPS
HP T1500 G4 INTL UPS
Output Power @ 230V
750 VA
525W
1000 VA
700W
1500 VA
1100W
AC Input power
• Rated input voltage
Single phase 220-240V
• Input voltage range
184 to 276V
• Input frequency range
45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
• Voltage
220/230/240V (-10% to +5%)
(1)
• Frequency
50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
• Standard
1 x 12V
9 Ah
2 x 12V
7 Ah
3 x 12V
9 Ah
Environment
• Operating temperature
range
0 to 35°C/32 to 95°F
• Storage temperature
range
-15 to +40°C /5 to 104°F
• Relative humidity
0 to 90% (without condensation)
• Noise level
< 40 dBA in normal mode
(1) Adjustable to 220/230/240V, but must be set to the identical AC power source value.
When the UPS is used in the EU area, use an external circuit breaker in front of the line with rating 16A,
250V which is IEC/EN 60898-1 standard compliant.
When the UPS is used in th NA area, use an external circuit breaker in front of the line with rating 20A, 250V.
Filter
Transformer
AVR
Charger
Inverter
Battery