Do not allow other cables or components to exert tension on fiber optic cables, which can be easily 

crushed or damaged. 

 

Avoid routing fiber optic cable around chassis and cabinet corners. If this is unavoidable, protect 
the cable. 

Routing network cable 

Network interconnects can involve a large amount of cabling due to the component/data path 

redundancy required to meet high availability goals. Network devices also require high serviceability, 

so cabling must be arranged to allow easy access to individual circuits. 
HP recommends the following guidelines for routing data cables: 

 

For components that must be movable while powered on, ensure that a full range of motion is 

possible without cable interference or disconnection. 

 

When securing cables inside the rack, dress the bundle in a way that avoids interference with 
installed components, rack side panels, or rails. 

 

Do not block access to field-replaceable components. 

HP Cable Management Kit 

HP offers a complete line of products that provide reliable, serviceable, and safe cabling options for 

assembling rack installations. Routing, securing, and protection solutions available from HP are listed 

in Table 2 and can be found at the main rack options product page at 

www.hp.com/products/rackoptions

6

 

Summary of Contents for P-FD8GBX2-V125W-FS - v125w 8 GB USB 2.0 Flash Drive

Page 1: ... Retention of excess cable 3 Protection of cables 3 Securing cables and connectors 3 Securing data cables 3 Securing power cables and connectors 4 Cable bend radius restrictions 4 Thermal issues with cable routing 5 Routing fiber optic cable 5 Routing network cable 6 HP Cable Management Kit 6 HP Factory Express services 7 For more information 8 Call to action 8 ...

Page 2: ...ure 1 can result in several types of issues Reduced performance due to signal crosstalk and interference across adjacent cables Difficult maintenance because components are blocked by cables Hazardous situations of damaged cables due to unchecked or unprotected movement Thermal cooling issues due to poor or restricted airflow around active components Any of the above situations can require unsched...

Page 3: ...ds of handling excess cables Run and attach excess cables for easy safe maintenance activities and proper operations Ensure that secured cables are not pinched damaged or kinked refer to the Cable bend radius restrictions section of this paper When possible use all cable management arms included in component kits Use HP cable management kits described later in this paper for maintaining and managi...

Page 4: ...cables with removable ties to prevent accidental removal of the cords from the system Figure 2 Example of retaining clamp system securing power cords on HP products Cable bend radius restrictions Routing cables typically requires looping excess cable or bending cable around chassis components The bend radius is defined as the minimum radius Figure 3 to which a cable may safely be bent without dama...

Page 5: ...increase sensitivity to noise For fiber optic cables micro bending of fibers that results in degradation of light transmission or breaking of fibers which results in loss of signal Thermal issues with cable routing HP rack mountable products that use forced air cooling typically draw cool air through the front of the chassis and push warm air out the back If this air flow is restricted in any way ...

Page 6: ...ommends the following guidelines for routing data cables For components that must be movable while powered on ensure that a full range of motion is possible without cable interference or disconnection When securing cables inside the rack dress the bundle in a way that avoids interference with installed components rack side panels or rails Do not block access to field replaceable components HP Cabl...

Page 7: ...outing The three levels within the trays allow for routing power data and fibre channel cables separately Rack to Rack Adjustable Cable Tray Aisle Transfer Bridge 383984 B21 Adjustable cable bridge used to transfer cables from the back of a rack across the datacenter hot aisle to the back of another rack Comes in a single size HP Factory Express services HP provides system integration services thr...

Page 8: ...o factory express Call to action Send comments about this paper to TechCom HP com 2007 Hewlett Packard Development Company L P The information contained herein is subject to change without notice The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services Nothing herein should be construed as constituting an additional w...

Reviews: