AC Input Power for NS7 Racks
This topic provides power specifications for AC input power in NS7 system racks.
Power Specifications
See...
Phase
Region
Single-Phase
North America/Japan
Three-Phase
Single-Phase
International
Three-Phase
CAUTION:
Be sure the hardware configuration and resultant power loads of each rack within
the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity. Note that circuit breaker ratings vary if your system includes an optional
rack-mounted UPS.
Table 3 North America/Japan Single-Phase Power Specifications
Modular PDU 1-phase
iPDU 1-phase
R5000 1-phase UPS
North America/Japan
24 A
24 A
4500 W
Output Load
200 – 240 V
200 – 208 V
200 – 208 V
Input Voltage
NEMA L6-30P
NEMA L6-30P
NEMA L6-30P
Input Connector
N/A
N/A
200 – 208 V
Output Voltage
4 x C19
6 x C19
1 x L6-30R
Output Connectors
(28 x C13)
(20 x C13)
4 x C19
4 x C13
UPS outputs are connected to the compatible PDU inputs.
Notes