NS7 Enclosure Power Loads
The total power and current load for a rack depends on the number and type of enclosures
installed in it. Therefore, the total load is the sum of the loads for all installed enclosures.
In normal operation, the AC power is split equally between the power feeds on the two sides (left
and right) of the rack. However, if AC power fails on one side of the rack, the power feed(s) on
the remaining side must carry the power for all enclosures in that rack.
NOTE:
For NS7 CG X2 power distribution, see
“DC Power Distribution for NS7 CG Systems”
Power and current specifications for each type of enclosure are:
Maximum Power
Consumption (VA)
2
Typical Power
Consumption (VA)
1
Power Lines per Enclosure
NS7 CG X2 Enclosure Type
2250
810
6
c7000 CG enclosure
300
300
-
BL460c Gen9 CG CPU
(64 GB RAM)
315
315
-
BL460c Gen9 CG CPU
(128 GB RAM)
330
330
-
BL460c Gen9 CG CPU
(192 GB RAM)
270
140
2
Gen9 Storage CLIM CG
265
135
2
Gen9 Networking CLIM CG ,
4C/1C (IP or Telco)
265
135
2
Gen9 Networking CLIM CG,
3C/2F (IP or Telco)
234
207
2
FDR IB ADI switch (must be
installed in separate rack)
7
7
32GB Memory kit
100
75
2
CG SAS disk enclosure,
empty
6
6
-
400GB SSD, 12G SAS, SFF,
SC
7
4
-
300GB, 15k rpm HDD, 12G
SAS, SFF, SC
40
35
1
CG Maintenance switch
(Ethernet)
420
210
2
Breaker panel
140
70
2
Fuse panel
10
5
2
Alarm panel
129
129
1
Rack-mount system console
(must be installed in separate
rack)
36
36
1
Console keyboard and
monitor
72