
NonStop i System with Cascading Rack-Mounted UPS and Data Center UPS
shows an example of a non-supported configuration in a NonStop i system with the
left PDUs connected to the rack-mounted UPS, and the right PDUs connected to a data center
UPS. To create a cascading UPS configuration, the rack-mounted UPS is connected to the data
center UPS.
Figure 22 NonStop System With Cascading UPS
A cascading UPS configuration presents potential problems. Problems attaining stability between
the pair of cascaded UPSs can cause unexpected and undesirable behavior. The control loops
of each UPS can interfere with the other.
A typical scenario where this behavior occurs is the failure of the smaller downstream UPS to
recognize a stable input from its upstream source. In the event of an upstream UPS failure or
output disturbance, the downstream UPS switches the load to battery. Once the upstream UPS
regains full function, the downstream UPS should recognize a stable input and switch to
pass-through mode; but this does not happen in all cases and some cases fail.
In a failing case, the downstream UPS fails to switch back to pass-through mode, instead running
from the battery until the battery set is drained. Once the battery is drained, the downstream UPS
must attempt to switch back up to pass-through mode. At the minimum, this leaves the downstream
UPS with depleted batteries.
Non-Supported UPS Configurations
75
Summary of Contents for Integrity NonStop i NS2300
Page 5: ...Ukraine RoHS material content declaration 79 Index 80 Contents 5 ...
Page 9: ...Figure 1 Example NS2300 System Configuration 42U 9 ...
Page 31: ...Figure 3 Intelligent PDU Connections Without UPS Power Distribution for NS2300 Systems 31 ...
Page 39: ...Figure 10 Example of Top AC Power Feed Without UPS Power Distribution for NS2300 Systems 39 ...