CAUTION:
To prevent improper cooling and thermal damage, do not operate the node unless all PCI riser cages
or rear I/O blanks are installed, and do not operate the node unless all PCI slots have either an
expansion slot cover or an expansion board installed.
FlexibleLOM 2U node riser cage assembly
Procedure
.
2.
Disconnect all peripheral cables from the node .
3. Remove the node from the chassis
4.
Place the node on a flat, level surface.
5.
Remove the FlexibleLOM 2U node riser cage assembly.
Three-slot riser cage assemblies
About this task
NOTE:
Three-slot riser cage assemblies feature different riser boards. For more information on the riser
board slot specifications, see "
PCIe riser board slot definitions
."
Procedure
.
2.
Disconnect all peripheral cables from the node .
3. Remove the node from the chassis
.
4.
Place the node on a flat, level surface.
5.
Remove the three-slot riser cage assembly.
FlexibleLOM 2U node riser cage assembly
51
Summary of Contents for Apollo 2000 System
Page 14: ...14 Customer self repair ...
Page 15: ...Customer self repair 15 ...
Page 16: ...16 Customer self repair ...
Page 17: ...Customer self repair 17 ...
Page 43: ... 1U right rear I O blank 2U rear I O blank Removal and replacement procedures 43 ...
Page 54: ... Intel Xeon Phi Coprocessor 5110P AMD FirePro S9150 GPU 54 Removal and replacement procedures ...
Page 57: ... AMD FirePro S9150 GPU AMD FirePro S7150 GPU Removal and replacement procedures 57 ...
Page 59: ... NVIDIA GRID K2 GPU Intel Xeon Phi Coprocessor 5110P Removal and replacement procedures 59 ...
Page 60: ... AMD FirePro S9150 GPU AMD FirePro S7150 GPU 60 Removal and replacement procedures ...