• Tertiary riser cage
To replace the component, reverse the removal procedure.
Removing and replacing a DIMM
To identify the DIMMs installed in the server, see "DIMM slot locations" in the server user guide.
Procedure
1.
Power down the server (
2.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
3.
Do one of the following:
• Extend the server from the rack (
Extend the server from the rack
• Remove the server from the rack (
Remove the server from the rack
on page 37).
4.
Remove the access panel (
on page 39).
5.
Do one of the following:
• Remove the air baffle (
• Remove the 4 LFF midplane cage (
Removing and replacing a 4 LFF midplane cage
on page 63).
6.
Remove the DIMM.
Removing and replacing a DIMM
73