Document 2.4.126, Revision 4
October 2017
20
Three-Phase Padmounted Distribution Transformers
Surge Arresters
Surge arresters can be used in three-phase
padmounted transformer installations to protect the
transformer and underground cable from damage
due to voltage surges.
Surge arresters should be installed only on
systems where the power frequency voltage at the
arrester does not exceed the published maximum
continuous operating voltage (MCOV) values.
Disconnect surge arresters before performing
impulse, induced-potential or applied-potential
tests; otherwise, the arresters may be damaged.
Reconnect surge arresters after testing and before
placing the transformer into service.
Internal MOV Arresters
Internal metal-oxide-varister (MOV) surge arresters
are designed to be fluid immersed and mounted
inside the transformer tank. It is recommended that
fluid-immersed MOV arresters not be exposed to an
average oil temperature exceeding 90°C (194°F)
and a maximum oil temperature exceeding 125°C
(257°F).
Disconnect fluid-immersed MOV surge arresters
before performing impulse, induced-potential or
applied-potential tests; otherwise, the arresters
may be damaged. Reconnect surge arresters after
testing and before placing the transformer into
service.
Optional arrester disconnectors provide a means
to disconnect the fluid-immersed MOV arrester
grounds for transformer testing without entering
the transformer tank. Individual disconnectors are
provided for each MOV arrester. Two different styles
of disconnectors are available, one manufactured
by ERMCO Components Inc. (ECI) and one
manufactured by Cooper Power Systems (CPS).
These two styles operate differently as indicated
below.
Before testing the transformer, disconnect the
arresters using the following procedure for the
disconnector on each phase.
1. Make sure the transformer tank is properly
grounded.
2. De-energize the transformer from a remote
location.
3. Ground all bushings and terminals.
4. Disconnect the MOV arresters by operating
the disconnectors as described below.
For the CPS disconnector (identified by a
black plastic external cap):
a. Unscrew the black disconnector cap
from the shaft.
b. Re-attach the small diameter end of
the disconnector cap to the shaft.
c. Push the handle and shaft toward
transformer until the shaft flange is
flush to the sealing gland.
For the ECI disconnector (identified by a
7/16” square brass metal head):
a. Unscrew the 7/16” square metal head
until the thread disengages.
b. Pull the shaft out to its full extent
(approximately 2”).
5. It is now safe to perform impulse, induced-
potential or applied-potential tests.
After testing the transformer, reconnect the MOV
arresters using the following procedure.
1. Make sure the tank is properly grounded.
2. De-energize the transformer from a remote
location.
3. Ground all bushings and terminals.
4. Reconnect the MOV arresters by operating
the disconnectors as described below.
For the CPS disconnector:
a. Pull the disconnector handle and shaft
fully away from transformer.
DANGER
FAILURE TO FOLLOW THE INSTRUCTIONS
BELOW WILL RESULT IN DEATH OR SERIOUS
PERSONAL INJURY, AND DAMAGE TO THE
EQUIPMENT.
• De-energize the transformer from a
remote location and make sure all
transformer terminals and bushings
have zero voltage before connecting or
servicing surge arresters.
• Disconnect all surge arresters before
performing impulse, induced potential or
applied potential tests.