- 9 -
Installation and Connection
Electrical connection/survey of supply lines
The electrical connection
must
be carried out by an authorised electrician in accordance with
existing rules and regulations.
The wiring diagram is located in the motor compartment.
The terminal for the electrical connection is located behind the right side plate.
An approved plug outlet or a safety cutout
must be located close to the oven so that
the oven can be disconnected during installation and repair. The safety cutout must be
able to cut off all poles with a total distance of break of at least 3 mm. Each of the two
units in a stacked arrangement (CombiPlus) must have its own plug outlet or safety cut-
out.
The warranty does not cover incorrect connection.
Supply lines - survey
(applies to all models (C, B, K, CPE, BPE, KPE)
(All cross sections in mm² )
1.06
1.06
1.08 - 1.10 -
1.12
1.08 - 1.10 -
1.12
1.16
1.16
1.20
1.20
2.10
2.14
2.10
2.14
9 kW
Fuse
18 kW
Fuse
24 kW
Fuse
36 kW
Fuse
27 kW
Fuse
400V 3N ~ 50/60 Hz
5x2,5
16A
5x4
35A
5x10
50A
5x16
63A
5x10
50A
400V 3 ~ 50/60 Hz
4x2,5
16A
4x4
35A
4x10
50A
4x16
63A
4x10
50A
415V 3N ~ 50/60 Hz
5x2,5
16A
5x4
25A
5x10
50A
5x10
50A
5x10
50A
440V 3 ~ 50/60 Hz
4x2,5
16A
4x4
25A
4x10
50A
4x10
50A
4x6
35A
200V 3 ~ 50/60 Hz
4x4
35A
4x16
63A
4x25
100A
4x35
125A
4x25
80A
230V 3 ~ 50/60 Hz
4x4
25A
4x10
50A
4x25
80A
4x35
100A
4x25
80A
230V 1 ~ 50/60 Hz
3x10
50A
3x25
80A
*
*
*
*
*
*
480V 3 ~ 50/60 Hz
4x2,5
16A
4x4
25A
4x6
35A
4x10
50A
4x6
35A
208V 3 ~ 50/60 Hz
4x4
25A
4x10
50A
4x25
80A
4x35
100A
4x25
80A
* Not possible
Recommended supply line:
H07RN-F