Start-up-, Service- and Operation Manual hotcontrol cDT+
Rev. 1.00.05
Subject to technical changes
13.11Temperature alarm Tmp
13.12Fuse failure Fus
13.12.1Phase missing FUS
Is one phase missing, the display in the view Standard shows a certain systematic. In the existing example for 12
zones phase L2 is missing. It is recommended to display 6 zones in parallel.
Phase L1 supplies Zone 1/4; Phase L2 supplies Zone 2/5; Phase L3 supplies Zone 3/6 on a HTC-Card.
Tmp
A temperature alarm is generated, when the actual temper-
ature value exceeds the parameter
value limit +5K for more than 5 seconds. The Heating of the
concerned zones is switched-off (
How it works
The parameter should be adjusted dependent on the mea-
surement range of the used thermocouple.
What good is it
A temperature alarm with subsequent disconnection avoids
damage on the device and provides the user with a specific
indication of the error in the hot runner.
Remedy
Reason
Trouble Shooting
Partial failure of sensor Incorrect actual value display, but no sensor short-circuit
Check sensor, exchange if necessary
Fus
The hot runner controller controls the status of fuses in the
heating circuit and output an error message in case of an
defective fuse.
How it works
The error message is displayed in the zone.
What good is it
The alarm fuse failure provides the user with a specific indi-
cation of the error. He can remove this without deviation and
delay.
Remedy
Reason
Trouble Shooting
Fuse defective
Check fuse on HTC-Card, replace if necessary (see chapter
HTC 06/15 Heating Thermocouple Card - Replace fuses)
Phase missing (see
chapter
Check mains voltage before fuse
Check circuit breaker
Check control fuse
In the first line of the zone display, the display
of the text alternates with the display of the
current value (see chapter
the hot runner controller is set into operation
and the heatings are ON.