No.
Sound Frequencies and Patterns
code
Description
EN54-3 Typ SPL@1m Typ Current
12345
28Vdc on axis
mA
see notes
12V
24V
12V
24V
1
800Hz to 950Hz swept at 120Hz
00000
Banshee Buzz LF
-
94
100
6
12
2
800Hz to 950Hz swept at 9Hz
10000
Banshee Fast Sweep LF
3
94
100
6
12
3
800Hz to 950Hz swept at 3Hz
01000
Banshee Slow Sweep LF
-
94
100
6
12
4
Continuous at 850Hz
11000
Banshee Continuous LF
-
94
100
6
12
5
830Hz to 970Hz swept at 9Hz
00100
Banshee Fast Sweep LF (New)
-
93
100
6
12
6
800Hz to 970Hz swept at 1Hz
10100
Medium Sweep LF
3
94
100
6
12
7
Continuous at 970Hz
01100
Continuous LF
-
94
99
6
13
8
Intermittant at 950Hz 1sec on, 1sec off
11100
Backup Alarm LF
-
93
99
7
14
9
Alternating 800Hz/1000Hz, 0.5sec each sound
00010
Alternate LF
-
94
100
6
13
10
800Hz/1000Hz swept at 0.5sec
10010
Medium Sweep LF
-
94
100
6
12
11
Alternating tones 800/950Hz at 3Hz
01010
Alternate LF
-
94
101
6
12
12
2400Hz to 2900Hz at 120Hz
11010
Banshee buzz HF
-
102
109
16
35
13
2400Hz to 2900Hz at 9Hz
00110
Banshee Fast Sweep HF
-
103
110
17
35
14
2400Hz to 2900Hz at 3Hz
10110
Banshee Slow Sweep HF
-
103
110
17
35
15
Continuous2900Hz
01110
Banshee Continuous HF
-
103
109
19
39
16
2450Hz to 3100Hz swept at 9Hz
11110
Banshee Fast Sweep HF (New)
-
103
109
18
36
17
Intermittant at 2900Hz 1sec on, 1sec off
00001
Backup Alarm HF
-
103
109
18
36
18
Alternating tones 2400/2900Hz at 3Hz
10001
Alternate HF
-
104
110
16
36
19
500Hz rising to 1200Hz over 3.5, silence 0.5sec
01001
Slow Whoop
3
95
101
6
12
20
1200Hz falling to 500Hz over 1sec, silence 10ms
11001
Din Tone (DK)
3
93
100
5
10
21
554Hz for 100ms and 440Hz for 400ms
00101
French Fire Sound
3
90
96
4
7
22
420Hz repeating 0.625sec on, 0.625sec off
10101
Australian Alert Signal
-
89
94
3
6
23
500Hz rising to 1200Hz over 3.75sec on, 0.25sec off
01101
Australian Evacuation Signal
-
95
101
6
12
24
950Hz for 0.5sec on 0.5sec off, for 3 phases, silence for 1.5sec
11101
US Temporal Tone LF
-
93
99
5
10
25
2900Hz for 0.5sec on 0.5sec off, for 3 phases, silence for 1.5sec
00011
US Temporal Tone HF
-
103
109
13
26
26
Intermittant 660Hz 150ms on, 150ms off
10011
Swedish Tone (Fire)
-
90
96
3
6
27
Continuous 660Hz
01011
Swedish Tone (All Clear)
-
91
97
5
9
28
Intermittant 970Hz 500ms on, 500ms off
11011
ISO8201 LF
-
90
96
5
10
29
Intermittant 2900Hz 500ms on, 500ms off
00111
ISO8201 HF
-
103
109
13
27
30
Yodel 800Hz/1000Hz, 0.25sec each frequency
10111
BT Banshee (FP1063.1)
-
94
100
6
12
31
Continuous 1000Hz
01111
BT Banshee (FP1063.1)
-
88
94
6
14
32
Bell Tone
11111
Bell Tone
-
94
99
12
25
• Volume control providing up to 20dB attenuation. All frequencies are nominal.
• Column EN54-3 shows tones approved under the construction Product Directive.
• Specifications with an* have not been verified to be EN54-3 compliant.
• Polar diagram information is available in the technical manual 85***99MD, available on request.
Banshee Excel Lite Xenon
TM
Sound Output Table
Every care has been taken in the preparation of this product release but no liability whatsoever can be accepted for the use of the information contained
therein. Hosiden Besson Ltd reserve the right to change or amend any design features in line with our policy of continuing development and improvement.
Iss 2
Deep base with
IP66 mounting
accessory
Shallow base
Specification
Termination:
1 x 8 way terminal block.
Screw terminals for 0.28mm
2
to 2.5mm
2
wire conductor
EN54-3 Voltage Range:
24VDC (20VDC to 28VDC)
Operating Voltage Range:
9VDC to 30VDC*
Tone Current Consumption:
See Sound output table
Tone Synchronisation:
Synchronised start
Flash Rate:
1/Sec
Flash Current Consumption: 90mA @ 12VDC
40mA @ 24VDC
Operating Temperature:
-20°C to +55°C
Case Material:
ABS
Environment Category:
Type A
IP Rating:*
Shallow Base IP45
Deep Base IP66
Units meet minimum requirements of IP21C Shallow Base
& IP33C Deepbase in accordance with EN54-3
Installation
All installation to be carried out by a competent person
IP66 Deep Base Moulding (weatherproof).
• To maintain IP rating when using a Deep Base, use wall mounting
bracket Part Number: MM08728. Do not drill fixing holes in deep
base. Use suitably rated 20mm cable glands to fit cables or conduit
via side knock-outs. Fit ‘O’-Ring seal between lens and base.
Non-IP66 Deep Base.
• Knock out the conduit/cable gland holes in side of deep base.
• Fit conduit or 20mm cable glands then screw the base to the
mounting surface or BESA box.
Shallow Base Moulding.
• Drill mounting holes in the bottom of Base for screw fixings.
• Route cable through rear hole or side knock-outs.
• Screw the base to the mounting surface or BESA box.
All fixings.
• Connect unit as shown in connection diagram (Left). Note: If
independent supplies are required for the sounder and the beacon
elements, remove LK1 and LK2.
• Place the Excel Lite onto the base and turn clockwise to retain.
• To remove the Excel Lite turn unit counter-clockwise.
• Where applicable, fit the security screw through the hole in the
side of the lens assembly.
Sound selection 1 to 5, output level
7 & 8, 6 not used
Connection diagram