25
1. Icemaker
• Icemaker water supply inlet is 1/2" female pipe thread (FPT). A minimum of 1/2" nominal
copper water tubing is recommended for the icemaker water supply line.
• An icemaker water supply line shut-off valve and drain valve should be installed.
• Icemaker drain outlet is 3/4" FPT. A minimum of 3/4" nominal hard pipe is recommended
for the icemaker drain line. Condensation drain outlet is 3/8" OD hard tube. The
condensation drain line can be connected to the icemaker drain line or can be run
separately.
KMH-2000SRH/3
Fig. 16
Remote Condenser
Line Set Connections
Separate piping to approved drain.
Leave a 2-inch (5-cm) vertical air
gap between the end of each pipe
and the drain.
Icemaker Water Supply
Line Shut-Off Valve
Icemaker Water Supply Line
Drain Valve
Icemaker
Icemaker
Water Supply
Inlet
1/2" FPT
Bin Drain Outlet
See Manufacturer's Instructions
2-inch (5-cm) air gap
Floor Drain
Icemaker
Drain Outlet
3/4" FPT
Bin
Vent Tube
Minimum 1/2" Nominal Copper Water Tubing
Minimum 3/4" Nominal Hard Pipe
Condensation
Drain Outlet
3/8" OD Hard Tube
Vent Tube