39
5. Bin Control Selector (S1 dip switch 7)
The appliance is factory set for infrared sensor bin control operation. No adjustment is
required. In the factory default position (S1 dip switch 7 in the on position), the gear motor
delay after the upper float switch closes is 30 sec.
WARNING! Do not place S1 dip
switch 7 in the off position. This could lead to icemaker movement or ice overflow.
S1 Dip Switch
Setting
Bin Control Application
Gear Motor Delay
No. 7
OFF
BC (mechanical stand-alone) (Standard Ice Storage Bins Only) 5 seconds
ON
BC (infrared sensor) and Mechanical Bin Control
(mechanical backup)
30 seconds
6. BC (Mech. Stand-Alone or Backup (only)) Shutdown Delay (S1 dip switch 8)
Not available when S1 dip switch 7 is on. Factory set for normal operation. No adjustment
is required. This appliance does not utilize a mechanical bin control.
S1 Dip Switch Setting
Mechanical Bin Control
Shutdown Delay
No. 8
OFF
0.25 Seconds
ON
6.7 Seconds
7. Shutdown Sequence (S1 Dip Switch 9)
Factory set for optimum performance. Do not adjust.
S1 Dip Switch
Setting
Shutdown Sequence
No. 9
OFF
Slow timing (90s after Mechanical Bin Control delay is satisfied, the COMP shuts
down; after an additional 60s, the GM shuts down)
ON
Fast timing (after Mechanical Bin Control delay is satisfied both COMP & GM shuts
down at the same time)
8. Factory Use (S1 Dip Switch 10)
Factory set for optimum performance. Do not adjust.