MAN0922-01-EN SmarMod Quick Start Guide
____________________________________________________________________________________
Page 12 of 14 1017
3. If communications is established and good then expect to see the value in
%R1006(7) increase.
4. If communications is established and bad then expect to see the value in
%R1004(5) increase. Check the cable connections and or register addressing in
Cscape/Protocol Configuratiuon/Scanlist
5. If there is no communications then %R1002 will increment. Check cable is
connected/XLt and SmartMod are powered and configured and that the XLt is in
RUN mode
6. For individual Modbus Nodes (SmartMods) another register can be enabled at
Cscape/Protocol Configuration/Device settings
as per Fig. 13
Fig. 13