Troubleshooting
Batteries_Rail_Power_Manual_en02.docx
41
10.3.
No battery voltage can be measured
If no battery voltage can be measured, proceed as follows:
Cause
Remedy
Main plug of the battery system is
not inserted
Connect the main plug
Main plug of the battery system is
defect
Replace the main plug
Cable breakage
Replace the cable
Cell connector(s) is/are defect
Replace the connector(s) (use new spring
washer(s))
10.4.
Malfunction of the temperature sensor
If the temperature sensor does not provide plausible temperature values in the range lower -
50 °C or higher 80 °C, proceed as follows:
Possible Cause
Remedy
Temperature sensor defect
Replace the temperature sensor
Plug defective
Replace plug
Plug not inserted
Insert plug
Cable breakage in the extension
cable
Replace cable