T
ECHNICAL
D
ATA
8029HEPTA-V2/GPS GPS - NTP Time Server with LAN Interface - V08.00
113 / 130
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
12
Technical Data
The company
hopf
reserves the right to hardware and software
alterations at any time.
12.1 General
– 8029HEPTA/GPS
General Data
– System 8029HEPTA/GPS
Housing design:
Sheet steel / Aluminium, closed
Housing dimensions:
See
Chapter 2.1 19 inch Rack 1U/84HP (Slim
Protection type of the housing:
IP20
Protection class:
I, with PE connection. Additional earth screw
for cables up to 16mm
2
Cooling:
Passive, ventilation slots left / right
Weight:
Approx. 3kg
AC Power Supply
(with wide input range)
Nominal input voltage:
100-240V AC / 47-63Hz
Connection via input connector compliant
with IEC/EN 60320-1/C14 with EMI line filter
and switch
Input voltage range:
85-264V AC
Frequency:
47-63Hz
Current consumption
(at nominal values):
Approx. 0.37A (120V AC) / 0.23A (230V AC)
Starting current:
Typ. 15A (I
O
= 100%) 120V AC
Typ. 30A (I
O
= 100%) 230V AC
Mains failure bridging
at nominal load:
> 20msec. (> 100V AC)
Turn-on time after application of mains
voltage:
< 500msec.
Transient overvoltage protection:
Overvoltage category II (EN 60664-1)
Input fuse - internal:
2A (equipment protection)
Recommended pre-fuse:
Line protection switch 6A, 10A
characteristic B (EN 60898)
PE leakage current:
< 0.75mA (60Hz, compliant with EN 60950)
Insulation voltage input / PE:
2000V AC,
1 minute, residual current = 10mA,
500V DC, 50M
at least (at room temperature)
Output Data (internal only)
Internal nominal output voltage:
5V DC
Nominal output current I
N
0°C .. +55°C:
3A
(U
OUT
= 5V DC)
Efficiency:
> 74%
(at 230V AC and nominal values)