8.3.6.14 Sync Status OC
The output of the status optical coupler (on the back panel of the Time Server
8029HEPTA/GPS) can be configured by the use of this function.
The Sync states are listed in this selection window in rising quality from the bottom to the top
(
SYNC
= optimal condition).
Behaviour of Optical Coupler:
•
Selected status achieved or better
– Optical coupler switched through
•
Selected status not achieved
– Optical coupler blocked
Value range
Optical Coupler Status
SYNC
Time synchr Quartz regulation started/running
SYOF
Time synchr SyncOFF running
SYSI
Time synchronized as simulation mode
(without actual GPS reception)
QUON
Quartz/Crystal time + SyncON running
QUEX
Quartz/Crystal time (in freewheel after synchronization
failure
Board was already synchronized)
QUSE
Quartz/Crystal time after reset or manual setting
INVA