RC-F
UNCTION
B
OARD
7406RC
D
ESIGN
12 / 27
7406RC Slave Clock Control Board for System 7001RC - V02.03
hopf
Elektronik GmbH
Nottebohmstr. 41 • D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
4.3
7406RC Board Assembly Overview
DS1 - DS2 : standard ex works (Standardeinstellung ab Werk)
X2
J1
J14
MB3
J5
J2
J4
J6
60V
48V
24V
J11
J12
J13
60V
48V
24V
J8
J9
J10
1 2 3 4 5 6 7 8
on
DS2
1 2 3 4 5 6 7 8
on
DS1
ST3
1
1
Del
ta R
ibbon
24
-p
o
le
fe
m
a
le
V
G
-l
e
dge
64
po
le
m
al
e
Description
Function
ST3
Service connector
X2
Diagnosis connector
J14, J6
Service jumper
MB3, J1
Operating voltage measuring points (5 V DC)
J8, J9, J10
Voltage monitoring setting for line 1
J11, J12, J13
Voltage monitoring setting for line 2
J2, J3
Diagnosis jumper line 1
J4, J5
Diagnosis jumper line 2
4.3.1 Line Voltage and Monitoring Device Configuration
The lines of RC Function Board 7406RC can be operated with various voltages. For this
purpose, jumpers 8-13 (see imprint) must be pre-set for voltage monitoring.
Jumper setting
Line 1
Line 2
Line voltage
Monitoring voltage
Line fault on insufficient voltage
J13
J10
24 V
18 V
J12
J9
48 V
36 V
J11
J8
60 V
45 V