3.4 Reserved Space Requirement
When installing the string inverter, the space around the string inverter must be reserved for heat
dissipation and maintenance.
≥
500mm
≥
300mm
≥
500mm
≥
200mm
≥
1000
mm
Figure 3-1 Single string inverter installation space
When installing multiple string inverters in a same surface, the side by side installation is
recommended.
≥
200mm
≥
200mm
Figure 3-2 String inverters side by side installation space
When installing multiple string inverters in two lines, the triangle installation is recommended.
≥
100mm
≥
300mm
≥
100mm
≥
300mm
Figure 3-3 String inverters triangle installation space