Optimization of the Settings
Basic Setting
(for hot water heating operating with temperature between
20 and 90 °C)
A
è
4
B
è
50
C
è
-8
n
During the regulation procedure open the radiator valves
completely. (Set the thermostat valves at the maximum va-
lue).
n
If in the test room (room where the temperature sensor is
located) radiator valves are installed, these must be left
open always.
n
Close all windows and doors.
n
Proceed gradually by making only small changes.
n
Wait for the outcome of the change after each setting
(approx. 1 h).
Depending on the type of system – radiator/convector heating
(up to 90 °C), low temperature heating, air heating, mixing cham-
ber regulation – and depending on the layout of the heating surfa-
ces various flow or supply temperatures are needed to reach the
right room temperature – and hence also different settings on the
setting knobs.