Honeywell XM500 Manual Download Page 6

XM500 TCP/IP MODEM

74-3468—3

6

TECHNICAL INSTALLATION AND SET-UP (OPTIONAL)

For ease of use, it is recommended to use the IP-Connect 

Software provided to configure the XM500 controller. 

However, if desired the XM500 may be configured manually. 

The following sections provide the technical details to 

configure the XM500 using Windows Terminal program.

IMPORTANT

For L

ON

S

TATION

™ and L

ON

S

PEC

™, refer to the 

L

ON

S

TATION

™ and L

ON

S

PEC

™ Configuration 

section on page 5.

Data Line Monitor

For every modem start-up, using a data line monitor is highly 

recommended in order to allow checking the communication 

and the RS-232 line status during commissioning.

RS-232 Breakout Box

As the XM500 does not provide LED indication of the line 

status of TxD, RxD and other control, using a standard 

RS-232 breakout box can be helpful.

Setting Up the XM500

1.

Start a terminal program and set it up for 9.600 bps.

2.

Enter <ATEV1><ENTER> and verify that the XM500 

returns <OK>.

3.

Enter the commands listed below in order to initialize 

the XM500 for the TCP/IP communication between XBS 

or L

ON

S

TATION

™ and EXCEL 5000/15 controllers:

a.

lockmem off 

: (unlocks nonvolatile memory).

b.

stty xxxxx 

: (sets RS-232 Baud Rate to xxxxx bps; 

default is 9600 bps; supported baud rates: 

2.400/4.800/9.600/19.200/38.400)

IMPORTANT

If baud rates 19.200 and 38.400 bps are to be used 

the autobauding MUST be switched <on> after the 

TCP/IP initialization has been completed.

c.

ifconfig

 160.221.71.130 255.255.252.0

This example is for an IP address 160.221.71.130 

with appropriate network mask 255.255.252.0. 

(note the blank space between IP address and 

network mask).

d.

route add net default

 160.221.68.1 1

(Example of a gateway definition)

Please check with the local network administrator if 

a gateway definition is necessary. The parameters 

are the default gateway address (160.221.68.1) and 

the number of hops to the gateway(1). They must be 

separated by a space

e.

lockmem on

 : (locks nonvolatile memory).

f.

autobaud on

 : (enables the XM500 to adapt its serial 

baud rate to that of the controller or the workstation 

central. This is only needed if baud rates 19.200 and 

38.400 bps are to be used for XL50.)

IMPORTANT

• Above user commands can only be recognized by 

the XM500 when the autobaud is <off>.

• This means that the autobaud <on> command 

MUST be used AFTER the user commands have 

been entered.

• If user commands should be changed, then FIRST 

autobaud must be set to <off>.

4.

Enter the following AT commands in order to initialize 

the XM500 for the required serial behavior.

AT Commands for XM500 Connected to XL5000 
Controllers with O.S. 2.01.00 or Later and for 
XBS via COM Port

ATE0X1&C1&D1

E0:echo off

(X1: ignore busy signal and dial tone, 

&C1: carrier-detect follows connection,

&D1: Hang-up on DTR transition)

AT&W

(save init profile in NVRAM)

AT Commands for XM500 Connected to 
Modem Devices XM100A, XDM506 and 
for XBS with XPC500 Card

ATE0V0X1&C1&D1

AT&W

(save init profile in NVRAM)

IMPORTANT

• Due to an initialization problem of the XBS for the 

XPC500 card, reliable remote communication can 

not be granted with XBS 1.4.4 or older in 

combination with XPC500.

• It is NOT recommended to use XM500 in 

combination with XPC500.

Summary of Contents for XM500

Page 1: ...ually via Windows Terminal Program The LAN WAN network server requires no software download for the XM500 FEATURES Communication between XBS or LONSTATION centrals and EXCEL 5000 controllers via standard Ethernet TCP IP LAN WAN TCP IP provides more reliable and faster communications than analog modem Compatible with all HVAC systems connecting through an SLTA 10 Compatible to EXCEL 5000 controller...

Page 2: ...emperature 14 to 158 F 10 to 70 C Relative humidity 10 to 95 non condensing Processor and Memory Main processor 68HC000 Ethernet Coprocessor SMC91C96 Memory RAM 64K byte with 2K byte NVRAM EPROM 256K byte Software IP Connect software is provided to configure the XM500 modem The various controllers and workstations are configured using Honeywell specific software for serial communication with EXCEL...

Page 3: ...l serve as the telephone number for the workstation or EXCEL controller that is connected to it EXAMPLE 160 221 71 130 NOTES 1 If communication is only done internally in the LAN unofficial IP addresses will be sufficient 2 If only dynamic IP addresses are available Use a DHCP server and have it allocate the identical IP address every time it does a dynamic IP address allocation 3 For an intermedi...

Page 4: ...blank configuration screen 13 When the modem is ready the status screen should read Please select device XM500 is connecting to 14 Choose the device which the modem is going to be connecting to or the workstation from which the modem is connecting NOTE If you are connecting from XBS make sure you choose the same baud rate as the controller to which you connect 15 Once you have chosen a device the ...

Page 5: ...em is not connected to a network LONSTATION and LONSPEC Configuration 1 Begin from the desktop 2 Double click My Computer 3 Double click Control Panel 4 Double click Modems 5 Click Add 6 Click the box Don t detect my modem I will select it from a list 7 Click Next 8 Under Manufacturers column click Standard Modem Types 9 Under Models column click Standard 28800 bps Modem 10 Click Next IMPORTANT De...

Page 6: ... an IP address 160 221 71 130 with appropriate network mask 255 255 252 0 note the blank space between IP address and network mask d route add net default 160 221 68 1 1 Example of a gateway definition Please check with the local network administrator if a gateway definition is necessary The parameters are the default gateway address 160 221 68 1 and the number of hops to the gateway 1 They must b...

Page 7: ...been initialized it will always and consistently show the same pre defined serial behavior Table 1 Hayes Command Set EXAMPLE Command ping 160 221 71 131 Answer 160 221 71 131 is alive This answer means that the TCP IP communication to the target XM500 is working If the target XM500 cannot be reached the answer will be no answer from 160 221 71 131 Command Description Hang up close connection A A0 ...

Page 8: ...ow control Cable Specifications RS 232 CABLE RJ45 TO DB9 DB25 IMPORTANT The RS 232 cable is a special calibration cable Standard RJ45 to RS 232 connectors will not work Table 3 PIN Assignment RS 232 Cable a Note that the DTR signal is looped back in order to supply DSR to the terminal XBS or EXCEL 5000 CPU ETHERNET CABLE Use a standard 10BASE T twisted pair Ethernet cable with RJ45 plugs LONSPEC a...