Honeywell XLS-278 Specification Data Download Page 3

XLS-270 AND XLS-278 MANUAL PULL STATIONS

3

EN0C-0741 0599R2-MA

SPECIFICATIONS

Models:

XLS-270:  One stage fire alarm station; English markings
XLS-270P: Two stage (pre-signal) fire alarm station;

English markings

XLS-278:  Double action, one stage fire alarm station;

English markings

Addressing Requirements:

XLS-270/270F/270B: 1 module address
XLS-270P/270PB: 

2 module addresses

XLS-278: 

1 module address

Operating Current:

XLS-270/270F/270B:

Standby: 250

µ

A

Activated: 400

µ

A

XLS-270P/270PB:

Standby: 396

µ

A

Activated: 680

µ

A

XLS-278:

Standby: 250

µ

A

Activated: 400

µ

A

Construction and Finish:

XLS-270xx:

Die-cast zinc; red epoxy with aluminum markings

XLS-278:

Lexan, red with white markings

Type Code:

Factory set

Operating Voltage:

15.2  to 19.95V dc (19V dc nominal)

Environmental Limits:

Temperature: 32° to 120°F (0° to 49°C)
Humidity: 0 to 93% rh

LED Operation:

On-board green LED: Flashes when polled
On-board red LED: Flashes when in alarm/ active
Both LEDs: on steady when in alarm (stand-alone)

Compatibility:

Use with Signature Loop Controller

Accessories:

276-GLR: 

20 glass rods; for XLS-278 only

27193-11:  Single Gang Surface mounting box

for XLS-270xx models only

276B-RSB:  Surface mounting box, red for XLS-278 only

Figure 1: XLS-270L

Figure 2: XLS-278

Summary of Contents for XLS-278

Page 1: ...atures a rugged Lexan housing XLS 270 models have traditional familiar appearance XLS 270 models are available for one stage GA two stage pre signal and double action Break glass operation on XLS 270 models Intelligent device with integral microprocessor Non volatile memory Automatic device mapping Electronic addressing Stand alone operation Diagnostic LEDs Designed for high ambient temperature op...

Page 2: ...ic LEDs Twin LEDs provide visual indication of normal and alarm active conditions They are visible only when the station is removed from the mounting box A flashing GREEN LED shows normal system polling from the loop controller A flashing RED LED means the station is in alarm active state Both LEDs on steady shows alarm state in stand alone mode Installation The Signature Series fire alarm manual ...

Page 3: ...XLS 278 Standby 250µA Activated 400µA Construction and Finish XLS 270xx Die cast zinc red epoxy with aluminum markings XLS 278 Lexan red with white markings Type Code Factory set Operating Voltage 15 2 to 19 95V dc 19V dc nominal Environmental Limits Temperature 32 to 120 F 0 to 49 C Humidity 0 to 93 rh LED Operation On board green LED Flashes when polled On board red LED Flashes when in alarm act...

Page 4: ...ome Building Control European Centre of Excellence Honeywell Inc Honeywell GmbH Fire Solutions Honeywell Plaza Honeywellstrasse Lovelace Road Southern Industrial Area P O Box 524 63477 Maintal 1 Bracknell Berkshire RG12 8WD Minneapolis MN 55408 0524 Germany United Kingdom EN0C 0741 0599R2 MA 4 ...

Reviews: