![Honeywell WebStat T7350 System Engineering Download Page 40](http://html.mh-extra.com/html/honeywell/webstat-t7350/webstat-t7350_system-engineering_2158902040.webp)
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
63-4368
40
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name
L
ON
S
PEC
™ Ref Name
Class
Description
nvoBypass
Bypass Out
OUT
The T7350H uses nvoBypass to command bypass to other XL10
nodes. When the T7350 is in bypass, it commands nvoBypass.
This is a one to many bound relationship. “Many” means one
T7350H can command bypass on all XL10s connected on the
subnet.
Reports whether this device is in timed bypass of the scheduled
occupancy state. Used by other devices to also bypass the time of
day schedule.
Value State Action
0 0 This device is not in bypass
Power up value
1 100 This device is in bypass
nvoData1
nvoData1
OUT
Reports Manufacturer Specific Device Data including:
bypassTime, coolStgsOn, DaysLeftKeypadHoliday, dischTemp,
effMode, effOccCurrentState, effSetPt, fan, heatStgsOn, oDTemp,
percentCmd,Cool, percentCmdHeat, spaceHumidity, spaceTemp,
subBaseType, sysMode, terminalLoad.
nvoData2
nvoData2
OUT
Reports Manufacturer Specific Device Data including: auxRelay,
DALimit, dehumidActive, ESR, holiday, noAuxHeat1, noAuxHeat2,
occSensor, relayAux, relayCool1, relayCool2, relayCool3,
relayFan, relayHeat1, relayHeat2, relayHeat3, remoteStPtOffset,
schedNextState, scheduledState, scheduledTuncos, stagesActive,
T7350CommWorks, temporarySetPt, totalError.
nvoDischAirTemp
Discharge Temperature
Out
OUT
The current discharge air temperature (Celsius). The sensor is
configured by nciConfig.dischAirSensor. A value of 327.67 means
the sensor is not functioning correctly or is out of range.
327.67: Power up value.
nvoEffectOccup
Effective Occ Out
OUT
Current effective occupancy state:
0: OC_OCCUPIED (power up value).
1: OC_UNOCCUPIED
2: OC_BYPASS
3: OC_STANDBY
-1: OC_NUL
nvoEffectSetpt
Effective Stpt Out
OUT
Effective room temperature control set point (Celsius).
327.67: Power up value.
nvoError
nvoError
OUT
Device error status. Refer to Appendix C - Network Error
Reporting for details.
nvoFileStat
File Status Out
OUT
File transfer status.
nvoHeatCool
Application Mode out
OUT
Effective operating mode:
0: HVAC_AUTO
1: HVAC_HEAT (heat or re-heat).
3: HVAC_COOL
6: HVAC_OFF (power up value).
7: HVAC_TEST (manual mode or cover in factory test mode).
8: HVAC_EMERG_HEAT