W7752D,E,F,G FAN COIL UNIT CONTROLLERS 

 INSTALLATION INSTRUCTIONS 

EN1B-0250GE51 R0111B 

2

 

Fig. 2. DIN rail mounting 

Power 

Input power provided must be 230 Vac (+10%, -15%), 50 or 
60 Hz for W7752D and E; 115 Vac (+10%, -15%), 50 or 
60 Hz for W7752F and G. 
 

 CAUTION 

Turn OFF power prior to connecting to or removing 
connections from any terminals to avoid electrical 
shock or equipment damage. 

 
Use the heaviest gauge wire available, up to 14 AWG (2.5 
mm

2

)

 

with a minimum of 18 AWG (1.0 mm

2

) for all power 

wiring. Strain relief/support must be provided for power wiring 
within 2-3/8 in. (60 mm) of controller connection. 
 

IMPORTANT 

To comply with CE requirements, with devices 
having a voltage range of 50 to 1000 Vac or 75 and 
1500 Vdc which are not provided with a supply cord 
and a plug or with other means for disconnection 
from the supply having a contact separation of at 

least 3 mm in all poles, the means for disconnection 
must be incorporated in the fixed wiring. 

 

LonWorks Communications 

The unit is equipped with a free-topology transceiver for 
communication on L

ON

W

ORKS

® networks. The L

ON

W

ORKS

 

network is insensitive to polarity, eliminating the possibility of 
installation errors due to miswiring. 
Different network configurations (daisy-chain, loop, and star 
configurations, or any combination thereof) are possible (see 
also Excel 50/500 L

ON

W

ORKS

 Mechanisms Interface 

Description, EN0B-0270GE51). 
 

IMPORTANT 

Do not bundle wires carrying field device signals or 
L

ON

W

ORKS

 communications together with high-

voltage power supply or relay cables. Specifically, 
maintain a min. separation of 3 inches (76 mm) 
between such cables. Local wiring codes may take 
precedence over this recommendation. 

 

IMPORTANT 

Try to avoid installing in areas of high electro-
magnetic noise (EMI). 

 
The unit must be wired to the L

ON

W

ORKS

 network using level 

IV 22 AWG (Belden part number 9D220150) or plenum-rated 
level IV 22 AWG (Belden part number 9H2201504) non-
shielded, twisted-pair, solid-conductor wire. When possible, 
use Honeywell AK3781, AK3782, AK3791, or AK3792 cable 
(US part numbers). See Excel 50/5000 L

ON

W

ORKS

 

Mechanisms (EN0B-0270GE51) for details, including max. 
lengths. Use wire with a min. size of 20 AWG (0.5 mm

2

) and a 

max. size of 14 AWG (2.5 mm

2

). 

 

Wall Modules 

A variety of Excel 10 wall modules can be used with W7752 
FCU Controllers. See T7460 Wall Modules Installation 
Instructions (95-7610) and T7560 Digital Wall Module 
Installation Instructions (EN1B-0146GE51) for details. 

 

W7752 FAN COIL UNIT CONTROLLER

W7752 FAN COIL UNIT CONTROLLER

TERMINATION

MODULE

9

9

10

10

11

11

12

12

 

Fig. 3. Termination module connection (daisy-chain network configuration) 

Summary of Contents for W7752D2007

Page 1: ...tions that allow clearance for wiring The controllers can be mounted on a panel with screws or by snapping onto standard EN 50 022 DIN rail 1 3 8 by 9 32 in 35 mm by 7 5 mm See Fig 1 for mounting dimensions See Fig 2 for DIN rail mounting The type and length of screw required for screw mounting depends upon the panel material used to mount the con troller The controller can be mounted either verti...

Page 2: ...k configurations daisy chain loop and star configurations or any combination thereof are possible see also Excel 50 500 LONWORKS Mechanisms Interface Description EN0B 0270GE51 IMPORTANT Do not bundle wires carrying field device signals or LONWORKS communications together with high voltage power supply or relay cables Specifically maintain a min separation of 3 inches 76 mm between such cables Loca...

Page 3: ... assignments for various actuator types Refer to job drawings for specific wiring diagrams IMPORTANT Screw type terminal blocks are designed to accept no more than one 14 AWG 2 5 mm2 conductor Multiple wires that are 14 AWG 2 5 mm 2 can be connected using a wire nut Include a pigtail with this wire group and attach the pigtail to the individual terminal block Fig 4 Terminal cover removal Wire to t...

Page 4: ...OSE RELAY COM RELAY 1 RELAY 2 RELAY 3 SUPPLY VOLT SUPPLY VOLT PWR RELAY IN D F MODELS ONLY PWR RELAY OUT D F MODELS ONLY W7752 FAN COIL UNIT CONTROLLER WALL MODULE CONNECTIONS LONWORKS NETWORK IN LONWORKS NETWORK OUT OCCUPANCY SENSOR CHANGEOVER CONTACT AIRFLOW CONTACT WINDOW CONTACT MOTION SENSOR OPEN OPEN CLOSE CLOSE COM COM HI MED LO HEAT COOL REHEAT RETURN POWER MAINS L N FAN 1 2 3 4 5 6 7 8 9 ...

Reviews: