background image

The  following steps for complete checkout and testing

of a  W7620 are described fully below. The procedures
are   as follows:

1.

Check  W7620  installation and wiring, including

power to the  W7620.

2 .

Start-up  W7620 (connect  S7610  POT  or
ZM7601/ZM7603   software)  and assign a network
node address and application (even when using
device in  a  nonnetworked  application). Refer to
W7620  Application  Manual,  Form  63-4220.

3. Test analog and digital input points

4. Test analog and digital output points.

5.  Verify parameter point values.

1 .

Verify that the connections  between  the  W7620
and peripheral  equipment   are secure.

2 .

Verify that  grounding is correct  in  accordance  with

GROUNDING in this 

guide as follows:

a.

Verify   that  each  W7620   case is grounded

when the  W7620s   are powered from

individual  transformers.

b.

Verify that all  W7620  cases  are  grounded
when the  W7620s   are powered  from   a
c - o n   transformer.

c.

Verify  that if  the application calls for grounded

transformer secondaries, that the grounded
side is connected to  earth-ground  on the
W7620 (TR  earth-ground).

d .

Verify  that neither of the CNAP network  wires
is grounded or  connected to the 24  Vac wires.

e.

Verify that  the  polarization  of the CNAP
network wires is correct, positive to positive
and negative to negative in  alI cases.

3 .

Verify the CNAP network termination and biasing

resistors   are installed in accordance with 47640
Network Interface Unit  specification  sheet

(63-4290).

4 .

Turn  on power and  verify that each  W7620 has at
least 20  Vac at Terminals TR and TR

earth-ground.

Testing physical points requires either the actual  sensor

be at a known  value  or  digital state,  or that a simulated
known  value  or digital state be applied to the input point
terminals.  In the case of physical output points, the output
condition of the controlled equipment must be known,
or the output terminals of the  W7620 can be measured
with  an indicating device or meter. The Hardware
Configuration  Data table shows all of the possible physical
points with  terminal  designation and use. The General
Guide for  Input/Output  Point Testing  table  can  be  used
to determine what can be  used  to provide inputs and

what to use to  measure outputs.

Input Point lest Procedures

1.

Read point value  through  the  S7610   POT or the

ZM7601/ZM7603   software  to verify approximate

analog  value or digital state. If the data is
acceptable,  proceed  to the next point.

2 .

For analog points that display FA (sensor  failure)
next to the  engineering  unit:

a.

Provide  a known measurable value to the input.

b.

Compare the input point value displayed on
the  POT or  ZM7601/ZM7603  software  with
the known value.

c.

If the difference between the two values
exceeds the acceptable  range,  isolate the

problem by taking  a  measurement  at the

input source, the conductors (e.g., cable,

wire), and the  W7620.

Example:

The  following is the procedure for input
Point 1 (SPACE  TEMP).

1 .

Measure the  input space temperature  in degrees
Fahrenheit  with another  source,  such  as  a
thermometer,  near  the  actual   sensor.

2 .

Verify that the  S7610  POT or the
ZM76Ol/ZM7603  software  value reads  the

expected  temperature.

3 .

If the accuracy of the measurement is in question,
measure resistance supplied by  the sensor at the
Space Sensor itself to fmd sensed value Terminal

Summary of Contents for W7620

Page 1: ...e ad ditional input point expansion on one board of up to two resistive inputs two digital inputs two voltage inputs one dry contact one extended 24 Vac input q W7622 Expansion Output Point Boards provide ad ditional output point expansion on one board of up to three analog outputs three digital outputs 0 T7660 Space Temperature Sensor provides up to one space temperature input one space temperatu...

Page 2: ... LIKE To COMMENT ON OUR PRODUCTS OR SERVICES PLEASE WRITEOR PHONE 1 YOUR LOCAL H O N E Y W E L L SALES OFFICE CHECK WHITE PAGES OF YOUR PHONE DIRECTORY ASK FOR THE RESIDENTIAL ANDBUILDING CONTROLSSALES REPRESENTATIVE 2 RESIDENTIAL AND BUILDING CONROLS CUSTOMER SERVICE HONEYWELL INC 1885 DOUGLAS DRIVE NORTH MINNEAPOLIS MINNESOTA 55422 612 542 7500 IN CANADA HONEYWELLLIMITED HONEYWELL LIMITEE 740 EL...

Page 3: ...generation The W7620 Single Zone Controller can be applied in a stand alone environment with distributed zone control and hard wired time of day functionality It can also be applied as part of a networked system via connection to the RS 485 CNAP network The CNAP network enables communication to multiple W7620 Zone Controllers as well as to other controllers such as the W7600 Control Module 47640 N...

Page 4: ...Figure 1 CNAP Network Diagram ...

Page 5: ...oliig system to an occupied mode when the control system is in an unoccupied mode Also it can be used to initiate a continuous unoccupied period The LED indicates the override status These zone sensors arefurnishedwithanRJ11connectorforlocaloperation of an S7610 POT Portable Operator s Terminal See the T7660A D Space Temperature Sensors Information and Installation sheet Form 63 4219 for m o r e d...

Page 6: ...Figure 3 POT Portable Operator s Terminal ...

Page 7: ... is likely to cause interference in which case the user at his own expense will be required to take whatever measures necessary to correct the interference I surface before removing the W7621 or W7622 expansion board from the antistatic bag Failure to do so might damage the board I Mount the controller in a location that allows clearance for wiring servicing and removal of the cover 1 Remove the c...

Page 8: ... Knockout for l 2 in conduit fittings h Double knockout for l 2 or 3 4 in conduit fittings Figure 4 W7620 Mounting STANDOFF HOLE PLASTIC STANDOFF 10 PIN CONNECTOR Figure 5 Mounting Additional Board 8 ...

Page 9: ...ll controller models are furnished with a terminal arrangement similar to that shown in this figure Pull the pair of CNAP communication cables to each controller on the network and connect to the screw terminals marked CNAP Figure 6 I N O T E I Power Wire Lengths 1 Power requircmcnts limit 24 Vac power transmission distance The following data can be used in calculating load versus wire length Devi...

Page 10: ... override on an output point to a desired value with the S7610 POT or ZM7601 ZM7603 software 2 Measure or observe the output condition e g fan turns on 3 If the output does not follow the command override condition isolate the problem by checking connections and measurements at the output destination as well as at the W7620 4 Clear the override condition Example The following procedure is for Fan ...

Page 11: ...round Testing physical points requires either the actual sensor be at a known v a l u eor digital state or that a simulated known value or digital state be applied to the input point terminals In the case of physical output points the output condition of the controlled equipment must be known or the output terminals of the W7620 can be measured with an indicating device or meter The Hardware Confi...

Page 12: ...arily provide a good ground The following provides grounding details 1 Earth ground one W7620 within a group of W7620s connected to a given transformer Connect the ground wire to the green ground screw on the W7620 chassis See Figure 7 connect the same side of the transformer secondary to the same terminal number on each W7620 2 Grounded Transformer Secondaries If the Transformer has a grounded se...

Page 13: ...ee 24 Vac source indicating digital response to call from same transformer All three Inputs can be used separately or together to determine the final state of input Outputs Analog O IO Vdc 20 mA maximum Relay expansion 2 0 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Relay base 1 6 amp maximum running 7 5 amp In rush at 30 Vac 50 or 60 Hz Temperature Ratings Ambient 40 to 110 F 4 to 4...

Page 14: ...bl Knockout for l 2 in conduit fittings Q Double knockout for 1 2 or 3 4 in conduit fittings Figure 8 W7620 Dimensions 14 63 4224 ...

Page 15: ...Base Unit with cover Input Expansion Boards Use with W7459 Economizer Logic Module modulating spring Damper Actuator ...

Page 16: ...td aar 18 mlnlstBr des Communlcstions du Canada Dear Customer Please send your comments and suggestions to We welcome your comments and suggestions for Improving Honeywell Inc this publication 8500 Bluewater N W Your assistance is greatly appreciated and will enable us to Albuquerque NM 87121 1958 provide better technical information for you ATTN Technical Editor HONEYWELL MINNEAPOLIS MN 55408 INT...

Reviews: