W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
63-2596—09
22
7.
HEAT PUMP INPUT - W7213, W7214
ONLY
Execute step one, Checkout Preparation.
—
Turn DCV MAX to mid position; set enthalpy potentiometer to A.
Free cool LED turns on.
Actuator drives to 45 degrees open.
W7213: Jumper TR to B.
W7214: Remove jumper from TR and O.
Free cool LED turns off.
Actuator drives fully closed.
Table 4. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator. (Continued)
Step
Checkout Procedure
Proper Response