Honeywell VRW2 Quick Start Manual Download Page 10

VRW2 DYNAMIC PRESSURE- REGULATING FLANGED CONTROL VALVES

62-3116—01

10

TYPICAL SPECIFICATIONS

23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING 

(HVAC)

23 09 00 Instrumentation and Control for HVAC

23 09 13 Instrumentation and Control Devices for HVAC

23 09 13.33 Control Valves

Multi-Turn, Dynamic Pressure-Regulating Wafer-Flanged 

Control Valve

Mounting and Wiring

1.

Valves shall be available with wafer-flanges for use with 

either ANSI/ASME 125/150 or ANSI/ASME 250/300 pipe 

flanges in sizes from 2-1/2 up to 6 inches (DN65 to 

DN150). Each wafer flange shall be usable with either of 

two successive pipe sizes.

2.

The valve shall have an integral differential pressure reg-

ulator to maintain constant pressure drop across valve 

seat to decouple valve flow from system pressure 

changes. Regulator will be constructed from 316 stain-

less steel with a rolling diaphragm and operate under 

positive pressure. Regulator shall be located above axis 

of pipe with 1/4-in. ISO test port fittings to allow pressure 

measurement and venting. Control accuracy shall be +/-

5% or better.

3.

Valves shall use a non-rising stem, characterized plug 

with equal percentage flow control characteristic. Valve 

trim shall be stainless steel.

4.

Valve bodies shall have static pressure rating of 580 psig 

(4000 kPa) at 248°F (120 C).

5.

Maximum operating differential pressure rating shall be 

no less than 58 psid. Close-off pressure shall be 100 

psid minimum, at no more than 0.2% leakage.

6.

Valve stem seals shall be a combination of EPDM and 

Nitrile O-rings.

7.

Actuators shall be six turn rotary type requiring neither 

crank-arm nor linkage and direct mount to the valve 

actuator bracket. 

8.

Actuators shall provide screw terminal wiring connec-

tions with adapters for flexible conduit where mechanical 

protection is required by local codes. 

9.

Valve actuator shall be capable of operating on 24 Vac 

Class II power, in both electronic fail-safe and stay-in-

place configurations. Actuator fail-safe action in the 

event of power failure shall be field-selectable normally 

open or normally closed.

Control

1.

The actuator shall provide two-position, floating, analog 

or digital proportional control. Analog proportional control 

refers to direct acceptance of 2-10 Vdc or a 4-20 mA 

input signal. Digital proportional control refers to direct 

acceptance of 24 Vac pulse-width-modulated input sig-

nal. Floating control refers to direct acceptance of 24 Vac 

pulsed open and close commands from a tri-state 

(SP3T) controller. Two-position control of non-fail safe 

actuators shall be in the form of 24 Vac power controlled 

by SPDT switch.Two-position control of fail safe actua-

tors shall be in the form of 24 Vac power controlled by 

SPST switch.

2.

Flow valve shall have minimum 50:1 rangeability with an 

equal percentage flow characteristic. Actuator shall have 

field-adjustable signal zero and span adjustments.

3.

Flow settings shall be field-selectable from 50 unique 

settings.

4.

Proportional and floating control actuators shall provide 

a 2-10 Vdc/4-20 mA feedback signal.

5.

Actuators shall provide analog proportional, PWM, float-

ing, or two-position control through wiring options.

6.

Actuation will be available with electronic fail-safe opera-

tion.

Other

1.

Valves may not be installed with stems below the hori-

zontal plane to prevent actuator damage due to stem 

seal leakage, or accumulation of particulate in the stem 

packing.

2.

A water filtration and treatment system shall be installed 

and operated according to the requirements of Division 

23 25 13, Water Treatment for Closed-Loop Hydronic 

Systems. These requirements shall meet or exceed 

European Norm VDI 2035. The presence of excess rust 

in the system will void the manufacturer's warranty.

3.

Run time shall be constant and independent of: load, 

temperature, and supply voltage (within specifications). 

4.

All valves and actuators shall be manufactured under 

ISO 9001 International Quality Control Standards. 

5.

Actuators shall have a one year warranty from date of 

installation.

6.

Accessories Identification tags shall be available for all 

valves; tags shall be indelibly marked with gpm, model 

number, and tag location.

7.

Valves and actuators shall be as supplied by Honeywell.

Balancing Valves (Mechanical 
section)

Balancing valve installation and commissioning shall not be 

required when dynamic pressure-regulating control valves are 

used throughout a building. The balancing report, as required, 

shall confirm design coil flow by direct measurement across (a 

representative sample of/all) coils in the building.

Summary of Contents for VRW2

Page 1: ...When used in a system with variable speed pump drives 3 way valves and coil bypass lines are not required Systems that utilize the capabilities of properly installed and adjusted pressure independent control valves may qualify for LEED points FEATURES Multi sized bodies from 2 to 6 inch pipes with wafer flanged connections Combination ANSI ASME Class 150 300 pressure rating Controls hot or chilled...

Page 2: ...low Capacity See Table 1 Body Pressure Rating maximum 580 psig 40 bar at 248 F 120 C Controlled Medium Water or Glycol solutions up to 50 Not suitable for combustible gases oil or steam Fluid Temperature Range 4 to 248 F 20 to 120 C Minimum Differential Pressure See Table 1 Maximum Differential Pressure 58 psid 400 kPa Close off Pressure 101 psid 700 kPa maximum 0 2 leakage Flow Characteristics Eq...

Page 3: ...75 0 30 0 VRW2L 5 6 DN125 DN150 16 5 8 422 13 1 4 338 7 1 8 180 148 0 70 0 Table 3 Model Selection Valve Regulated Pipe fitting Body Pattern Valve Size Flow Rating Pressure Rating Valve Trim Actuator Secondary Spec Actuator Control Form Description VR Dynamic pressure regulated control valve W Combination size wafer flange 2 2 way J Valve size 2 1 2 and 3 in DN65 and DN80 K Valve size 3 and 4 in D...

Page 4: ...e a trained experienced licensed service technician 4 After installation is complete check out product opera tion as provided in these instructions Preparation CAUTION Equipment Damage Hazard Foreign particles like sand and metal chips can damage valve seals and regulator diaphragm For trouble free operation of the product good installation practice must include initial system flushing and chemica...

Page 5: ...ximum Flow Dip Switches so that the actuator limits the valve position to the maximum flow rate required Select the actuator dipswitch setting from Table 4 If adjusting the Dip Switch settings after power has been connected press the Reset Button to input the new setting ORIENTATION OF ACTUATOR ABOVE THE VALVE SPINDLE CORRECT M31296 DN 65 80 INCORRECT DN 65 80 85 85 M29519A M31286 1 ON 2 3 4 5 6 1...

Page 6: ...8 176 11 1 257 16 21 301 19 0 OFF ON ON ON OFF ON 2 7 84 8 5 4 113 7 1 125 7 9 179 11 3 263 16 59 310 19 6 ON OFF ON ON OFF ON 2 8 86 2 5 4 115 7 3 126 8 0 181 11 4 269 16 97 320 20 2 OFF OFF ON ON OFF ON 2 9 87 7 5 5 117 7 4 128 8 1 184 11 6 276 17 41 329 20 8 ON ON OFF ON OFF ON 3 0 89 1 5 6 119 7 5 130 8 2 187 11 8 282 17 79 339 21 4 OFF ON OFF ON OFF ON 3 1 90 0 5 7 121 7 6 131 8 3 189 11 9 28...

Page 7: ...6 8 148 9 3 146 9 2 221 13 9 363 22 90 445 28 1 ON ON OFF OFF ON OFF 5 4 108 6 8 149 9 4 146 9 2 221 13 9 364 22 96 448 28 3 OFF ON OFF OFF ON OFF 5 5 108 6 8 150 9 5 147 9 3 221 13 9 365 23 03 452 28 5 ON OFF OFF OFF ON OFF 5 6 109 6 9 151 9 5 147 9 3 221 13 9 366 23 09 455 28 7 OFF OFF OFF OFF ON OFF 5 7 110 6 9 153 9 7 147 9 3 221 13 9 367 23 15 458 28 9 ON ON ON ON OFF OFF 5 8 111 7 0 154 9 7 ...

Page 8: ...inks once 3 Release the Reset Button The indication LED should remain illu minated 4 Apply the new zero voltage to terminal 3 Any value between 0 7 Vdc 5 Press and release the Reset Button to memorize this value The LED should blink once as confirmation 6 Apply the new maximum voltage to terminal 3 Any voltage between 3 10 Vdc and at least 3 Vdc greater than the zero value 7 Press and release the ...

Page 9: ...ures At a given shaft position flow through the valve will constant as defined by the formula where ρ is the density of the glycol mix PIN changes constantly in a multi zone system as other valves open and close changing system flow and head pressure according to the characteristics of the supply pump curve Reaction of the mechanical pressure regulator is instantaneous eliminating changes in room ...

Page 10: ...Analog proportional control refers to direct acceptance of 2 10 Vdc or a 4 20 mA input signal Digital proportional control refers to direct acceptance of 24 Vac pulse width modulated input sig nal Floating control refers to direct acceptance of 24 Vac pulsed open and close commands from a tri state SP3T controller Two position control of non fail safe actuators shall be in the form of 24 Vac power...

Page 11: ...VRW2 DYNAMIC PRESSURE REGULATING FLANGED CONTROL VALVES 11 62 3116 01 ...

Page 12: ...Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 Honeywell Limited Honeywell Limitée 35 Dynamic Drive Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2010 Honeywell International Inc 62 3116 01 M S 02 10 Printed in U S A ...

Reviews: