Honeywell VR4920Z 1000 Instruction Sheet Download Page 6

6

EN1R--9181 0104R1--NE

The High--Low is provided with an earth terminal.
The High--Low is provided with quick connect terminals which

are suitable for 6.3 mm (

1

/

4

”) receptacles (e.g.series “250”

fasteners).
Also mPm type 122 connectors are to be used.

Ordernumber:

45.900.416--002

. . . . . . . . . . . . . . . . . . . . . . . . . .

NOTE: Good and reliable performance of the High--Low

regulator is not only dependent on the High--Low

itself, but also upon the reliability of the controller.

Enclosure (including cover)

IP 40

Electrical data

Supply

voltage

(Vac)

Color of

coil

Current

(mA)

Power

consumption

(W)

220/240 V,

50 Hz

black

17.4/19

3/3.2

The High/Low regulator should never be covered in such

a way that temperature will raise beyond acceptable

limits.

38

85

6.3 mm AMP

terminals

Cap
Adjustment screw for

maximum pressure setting
Adjustment screw for

minimum pressure setting

Earth terminal

Fig. 4.

ADJUSTMENT AND CHECKOUT

VR4920P

IMPORTANT

Adjustments should be made by qualified persons

only.
If the appliance manufacturer supplies checkout

and/or service and maintenance instructions,

carefully follow them. If such instructions are not

provided, then follow the procedure as outlined

below.
Allow time for pressure to stabilize before making

adjustments.
It is recommended that the High--Low regulator is

operated a few times to ensure correct setting.
It should be prevented, that High--Low regulator is

exposed to unneccessary forces because of wiring.
Cap has to be removed by putting a small screw

driver in one of the slots and lifting the cap carefully

while at the same time supporting the cap opposite

to the screw driver, (see fig. 5. page 7).

WARNING

Maximum pressure setting must first be adjusted then

minimum pressure setting can be adjusted.
Any adjustment of maximum pressure setting

influences minimum pressure setting.
Never adjust the maximum setting above the range

specified

Pressure taps

The gas control is provided with a pressure tap of 9 mm outer

diameter at inlet and outlet side.

When checking the pressure undo the screw a half turn and

slip the tubing over the nipple.

Ensure that screw is retightened after making the test.

Pilot flame adjustment (if applicable)

The gas control is packed for shipment with pilot flow at

maximum. Refer to the pilot burner or appliance

manufacturer’s instructions for recommended size of pilot

flame.

If adjustment is required turn pilot adjustment screw clockwise

to decrease or counter--clockwise to increase pilot flame.

Adjusting maximum pressure setting (see fig. 4. page 6)

Connect a suitable pressure gauge to pipe line or to outlet

pressure tap of gas control concerned, to measure burner

pressure (measuring point must be as near to burner as

possible).

Energize High--Low regulator, set gas control in operation

and wait until an outlet pressure is recorded on pressure

gauge.

Use a 8 mm wrench to turn adjustment screw for maximum

pressure setting clockwise to increase or

counter--clockwise to decrease pressure, until desired

maximum burner pressure is obtained.

Check maximum pressure setting after several times.

Summary of Contents for VR4920Z 1000

Page 1: ...ed to guarantee good burner performance in case the modulating control should become out of range The VR4920M is designed to work together with the W9335 modulating Modureg control W4115 logic control T7335A thermistor temperature sensor and an advanced range of micro computer based modulating controls The VR4920P provides the following functions Servo pressure regulation Outlet pressure is held a...

Page 2: ...et B Outlet C Inlet pressure tap D Outlet pressure tap E 6 3 mm terminals G Mounting holes M5 for connecting flanges H Earth screw K Pilot outlet connection L Pilot flow adjustment screw M Optional for inlet pressure tap 1 8 BSPT Fig 2 Dimensions VR4929M VR4920P ...

Page 3: ...nlet and outlet with an approved leak detection fluid If another gas leak is detected tighten adapter screws joints and pipe connections Replace the part if gas leak can not be stopped CAUTION Keep leak detection fluid away from electrical connections SPECIFICATIONS VR4920M Model VR4920M line voltage gas control fast opening with electric modulating regulator V7335A Ambient temperature 0 70 _C Min...

Page 4: ...and maintenance instructions carefully follow them If such instructions are not provided then follow the procedure as outlined below Allow time for pressure to stabilize before making adjustments It is recommended that the Modureg is operated a few times to ensure correct setting Remove cap before adjustment Take care that after any adjustment the cap is mounted WARNING The minimum pressure settin...

Page 5: ...e gauge to pipe line or to outlet pressure tap of gas control concerned to measure burner pressure measuring point must be as near to burner as possible Energize operator set control in operation and wait until an outlet pressure is recorded on pressure gauge Make sure Modureg is wired in the circuit Bring system in fixed setting mode Adjust current as low as needed to obtain the lowest pressure b...

Page 6: ... removed by putting a small screw driver in one of the slots and lifting the cap carefully while at the same time supporting the cap opposite to the screw driver see fig 5 page 7 WARNING Maximum pressure setting must first be adjusted then minimum pressure setting can be adjusted Any adjustment of maximum pressure setting influences minimum pressure setting Never adjust the maximum setting above t...

Page 7: ...wise to increase or counter clockwise to decrease pressure until desired minimum burner pressure is obtained Wire High Low regulator coil in circuit Check maximum pressure setting and re adjust if necessary Check minimum pressure setting again When High and Low pressure settings are correct replace cap Checkout Set appliance in operation after any adjustment and observe several complete cycles to ...

Page 8: ...R 9181 0104R1 NE Home and Building Control Combustion Controls Center Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel 31 591 695911 Fax 31 591 695200 http europe hbc honeywell com ...

Reviews: